47
7.5 Safety Mode With Contactor Monitoring
NOTE!
Make sure that the ESPE is ideally aligned. This is easiest to see in the “safety mode without
contactor monitoring” configuration
(see section “7.1 Initial Start-Up” on page 37)
.
Procedure:
Wire the emitter.
Disconnect supply power.
Connect supply power.
DIAG3 lights up.
Interrupt safety field within 30 s
(beginning at the cable connection
up to the other end).
SIG LOW/
DIAG4
DIAG3
EDM/DIAG2
SYNC/DIAG1
ERROR
RES
OSSD OFF
OSSD ON
K2
0 V DC
24 V DC
K1
K2
K1
Display at Receiver
Functions activated,
the receiver reboots.