Mounting
7
5.2
Electrical data
6
Mounting
For dimensions and mounting see “Zeichnungen / Drawings / Dessins”
page 11.
7
Commissioning
Before commissioning make sure that:
• the appliance has been mounted according to instructions,
• the electrical connections have been carried out correctly,
• the appliance is not damaged in any way.
8
Servicing
The appliance is maintenance-free
9
Cleaning
Zone 1:
• Clean only with a damp cloth using water or mild non-chafing, non-
scratching cleaning fluid. Never use aggressive substances or solvents
when cleaning.
Zone 21:
• Clean with a cloth, brush, vacuum-cleaner or similar. For wet cleaning use
water or mild non-chafing, non-scratching cleaning fluid. Never use
aggressive substances or solvents when cleaning.
10
Disposal
Observe national waste disposal regulations when disposing of the appliance!
Temperature range
-40 °C ... + 50 °C
Duty cycle
70%
Protection type according to IEC 60529
IP 65
Explosion protection
for gas
II 2G EEx me II T5
Explosion protection
for dust
II 2D IP65 T 70 °C
Test certificate
BVS 03 ATEX E 118X
Type
Rated current
Voltage range
Current
consumption
Fuse to be
connected in series
761 000 55
24 V=
21,6 ... 26,4 V
350 mA
F 0,5 A
761 000 65
24 V~, 50 Hz
21,6 ... 26,4 V
450 mA
F 0,63 A
761 000 66
42 V - 48 V~, 50 Hz
37,8 ... 52,8 V
220 mA
F 0,315 A
761 000 67
115 V~, 50/60 Hz
120 V~, 60 Hz
102,5 ... 126,5 V
108 ... 131 V
205 mA
220 mA
F 0,315 A
761 000 68
230 V~, 50 Hz
208 ... 250 V
70 mA
F 0,125 A
310_761_003_0305_A5.fm Seite 7 Mittwoch, 16. März 2005 4:35 16