FALL PROTECTION

USER INSTRUCTIONS

10K ZINC PLATED SWIVEL ANCHOR

Complies with ANSI Z359.18 Type A standard and

OSHA 29 CFR 1910 and 1926 regulations.

OPERATION AND INSTRUCTION MANUAL

  

Swivel Anchor Models: A510003, A510001, A320003, A510022

Additional Models: A320004, A320005, A510004, A570007, A510021, 

A510023, A350000

Page 1

WARNING:

 

ALL USERS OF THIS EQUIPMENT MUST READ AND 

UNDERSTAND  ALL  INSTRUCTIONS.  FAILURE  TO  DO  SO  MAY 

RESULT  IN  SERIOUS  INJURY  OR  DEATH.  USERS  SHOULD  BE 

FAMILIAR  WITH  PERTINENT  REGULATIONS  GOVERNING  THIS 

EQUIPMENT. ALL USERS OF THIS PRODUCT MUST BE PROPERLY 

INSTRUCTED  ON  HOW  TO  USE  THE  DEVICE.  AVOID  CONTACT 

WITH PHYSICAL HAZARDS (THERMAL, CHEMICAL, ELECTRICAL, 

ETC.). MAKE ONLY COMPATIBLE CONNECTIONS.

V4.7-E

Patent # US 8,424,638 

Summary of Contents for A320003

Page 1: ...005 A510004 A570007 A510021 A510023 A350000 Page 1 WARNING ALL USERS OF THIS EQUIPMENT MUST READ AND UNDERSTAND ALL INSTRUCTIONS FAILURE TO DO SO MAY RESULT IN SERIOUS INJURY OR DEATH USERS SHOULD BE FAMILIAR WITH PERTINENT REGULATIONS GOVERNING THIS EQUIPMENT ALL USERS OF THIS PRODUCT MUST BE PROPERLY INSTRUCTED ON HOW TO USE THE DEVICE AVOID CONTACT WITH PHYSICAL HAZARDS THERMAL CHEMICAL ELECTRI...

Page 2: ...diately USE LIMITATIONS This anchorage connector has been tested in compliance with the requirements of ANSI ASSE Z359 7 Compliance testing covers only the hardware and does not extend to the anchorage and substrate to which the anchorage connector is attached The anchorage connector must not be used outside its limitations or for any purpose other than that for which it is intended If this anchor...

Page 3: ...es 76 2mm 1 inch 25 4mm Minimum Breaking Strength MBS 10 000 lbf 44kN Weight 1 2 lbs 544 3g Materials Zinc Plated Steel Regulatory Compliance Meets or exceeds ANSI Z359 18 Type A ANSI Z359 7 19 OSHA 29 CFR 1926 502 OSHA 29 CFR 1910 140 LOADING CONDITIONS DIAGRAM ACCEPTABLE ACCEPTABLE IMPROPER ACCEPTABLE Page 3 ...

Page 4: ...ade 5 an 8 or equivalent bolt no shorter than 4 inches 100mm with a locking nut and washer must be used Swivel anchor must be flush with steel surface A 16mm bolt may be used in place of a 5 8 11 inch for metric applications 1 Use a proper drill and bit for steel 2 Drill a 5 8 inch 16mm hole no less than 75 inch 6mm deep 3 inches 76mm away from any edge 3 Hole must be straight and perpendicular to...

Page 5: ... straight perpendicular to surface 4 Hole must be free of debris 5 Concrete strength must be at least 3000psi 20 7MPa and no less than 7 inches 178mm thick 9 229mm drill 3 4 19mm Ø min from any edge 178mm min Embedment Depth min 114mm Torque 110 ft lbs 149Nm MODELS A510001 A510004 A510022 A510023 A350000 Page 5 9 inch 229mm min from any edge drill 3 4 inch 19mm Ø 7 inches 4 5 inches ...

Page 6: ...rson Back Plate to be used with 5 8 inch 16mm bolts or all thread Drill hole perpendicular into surface so bolt can pass freely through the substrate Nut must be fully threaded on the bolt to insure maximum strength ratings and integrity of anchor Bolt or All thread and Nut not included with Back Plate Torque Range 75 to 90 ft lbs 100 120Nm Grade 5 or 8 bolt 5 8 11 x 1 3 4 inch 3 8 inch min 9 5mm ...

Page 7: ...se meeting Sinopec specification Q SH303 242 2007 or equivalent 1 Strip decking to expose the Straight Loop Insert 2 Ensure that anchorage was properly installed Orange indicator should be flush with concrete surface and at least 9 inches 23 cm from any edge or corner Concrete should be at least 8 inches 20 cm thick and cured to a minimum of 3000 psi 20 7 MPa 3 Remove plastic bolt and o ring using...

Page 8: ...ge is attached to must be able to support 10 000 lbf 44kN and installed under the supervision of a qualified person MINIMUM CLEARANCE 2 feet 6m DECK FLOOR GROUND LEVEL WARNING SWING FALLS MAY OCCUR WHEN THE WORKER IS NOT DIRECTLY UNDER ANCHOR POINT Only use connecting subsystems that limit the maximum arrest force to less that 1 800 lbf 8kN In the EU these forces must be limited to 1350 lbf 6kN Pa...

Page 9: ...ete Bolt Assembly A510001 Swivel with Concrete Bolt Assembly A570007 Weld on Mounting Kit A320005 Backing Plate Only A510022 Swivel with Straight Loop Insert Bolt Assembly A510023 Straight Loop Insert Bolt Assembly A350000 Swivel with Steel Bolt Assembly and Concrete Bolt Assembly A510021 Straight Loop Insert A510003 Anchor Swivel 10K Page 9 ...

Page 10: ...ove If inspection reveals any damage that could affect the strength or operation of the device inadequate maintenance or an unsafe condition proper disposal is required The anchorage connector must be tagged unusable and then properly discarded MAINTENANCE CLEANING AND STORAGE Cleaning periodically may help prolong the life and proper functioning of the product The frequency of cleaning should be ...

Page 11: ...NOTES ...