Parameter
Name
Description
Default
Range
Unit Modbus
Address
Par.
Type
Min Cycles
Set the minimum number of On cycles and off cycles for
burst firing
8
0 to 999.9
n°
20
Read
Write
Soft Start
Set the duration of the soft start in increment of 50mSec. The
power controller ramps set to point changes over the time
set here. For more information see “Soft Start” page on this
manual
100
(5 sec)
0 to 255
(0 to
12,75 sec)
23
Read
Write
Delay
Set the firing delay degrees. Applies to burst firing with delay
trigger
1
1 to 255
°
23
Read
Write
Cycle time
Set the duration of one on-off cycle in increments of 50mSec.
Applies to zero crossing
60
(3 sec)
0 to 255
0 to 12,75
sec)
24
Read
Write
Control
Mode
(Feed-back)
Choose the feed-back type
1
19
Read
Write
Option
Description
Value
Voltage ²
Voltage squared
0
None
No feed-back
1
Current ²
Current squared
2
Voltage
Voltage
32
Current
Current
64
Power
Power
128
External
External signal via analog input 2
256
DEFAULT: None
1
Parameter
Name
Description
Default Range Unit Modbus
Address
Par.
Type
Prop band
power
Set the gain for the main loop. A smaller proportional band yields
a larger adjustment for a given deviation
10%
0 to
255
%
26
Read
Write
Integral
power
Set how aggressively the integral part of the control algorithm
acts. A smaller settings yields a larger adjustment for a given
deviation over a given time
50
0 to
255
27
Read
Write
Prop band
current
Set the gain for the main loop. A smaller proportional band yields
a larger adjustment for a given deviation
10%
0 to
255
%
63
Read
Write
Integral
current
Set how aggressively the integral acts in the current loop. A
smaller settings
50
0 to
255
64
Read
Write
Htr Break
sensitivity
Set the threshold of resistance that activates the Heater
Break alarm. This setting is in percentage of the nominal load
resistance
100%
0 to
100.0
%
29
Read
Write
Htr Break
delay
Set a delay between when the resistance drops below the value set
for a heater break sensitivity and when the heater break alarm is
indicated. This set increments of 50mSec
50 (2,5
sec)
0 to
255
(0 to
12,75
sec)
28
Read
Write
Logging
Enable or disable data logging on the internal SD card
0
139
Read
Write
Option cont.
Value
Phase angle Soft Start
20
Burst Firing Delay Trigger
35
DEFAULT: Burst Firing
3