Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 149
Output 7 Retransmit Input 2 Maximum
Value For Loop 2 Retransmit Maximum
Dec
2461
18845 37690
RW
Displayed value at which the retransmission output reaches its
maximum level (e.g. 2mA if type is 4-20mA).
Adjustable from -9999 to 9999.9
Hex
099D
499D
933A
Loop 1 Setpoint Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Loop 1 Setpoint Minimum
Minimum Allowed Setpoint For Loop 1
Dec
3944
20328 40656
RW
Valid between the scaled input lower & upper limits
Hex
0F68
4F68
9ED0
Loop 1 Setpoint Maximum
Maximum Allowed Setpoint For Loop 1
Dec
3945
20329 40658
RW
Valid between the scaled input lower & upper limits
Hex
0F69
4F69
9ED2
Loop 1 Main Local Setpoint Value
Main Setpoint Value For Loop 1
Dec
3960
20344 40688
RW
Valid between Setpoint Maximum and Minimum
Hex
0F78
4F78
9EF0
Loop 1 Main Local Setpoint Offset
Offset Of Main Setpoint Of Loop 1
Dec
3961
20345 40690
RW
Changes effective setpoint (for multi-zone slaves. +ve values
added -ve values subtracted.
Setpoint always limited by Setpoint Max and Min.
Hex
0F79
4F79
9EF2
Loop 1 Alternate Local Setpoint Value
Alternate Setpoint Value For Loop 1
Dec
3962
20346 40692
RW
Valid between Setpoint Maximum and Minimum
Hex
0F7A
4F7A
9EF4
Loop 1 Alternate Local Setpoint Offset
Offset Of Alternate setpoint Of Loop 1
Dec
3963
20347 40694
RW
Changes effective setpoint (for multi-zone slaves. +ve values
added -ve values subtracted.
Setpoint always limited by Setpoint Max and Min.
Hex
0F7B
4F7B
9EF6
Loop 1 Main Setpoint Source
Value
Main Setpoint Source For Loop 1
Dec
4050
20434 40868
RW
0
Local Setpoint 1
Hex
0FD2
4FD2
9FA4
1
Not Used
Loop 1 Alternate Setpoint Source
Value
Alternate Setpoint Source For Loop 1
Dec
4051
20435 40870
RW
0
Not Used
Hex
0FD3
4FD3
9FA6
1
Local Setpoint 2
2
Input 2 Remote Setpoint
3
Input A Remote Setpoint
Loop 1 Setpoint Select
Value
Setpoint Select For Loop 1
Dec
4122
20506 41012
RW
0
Main Setpoint
Hex
101A
501A
A034
1
Alternate setpoint
Loop 1 Setpoint Ramp Rate
Setpoint Ramp Rate For Loop 1
Dec
4123
20507 41014
RW
0 to 10000 display units per hour
(1 to 9999 is ramp rate per hour, either 0 or >10000 = Off)
Hex
101B
501B
A036
Loop 1 Target Setpoint
Actual Setpoint Value Of Selected Loop 1 Setpoint
Dec
4125
20509 41018
RO
The Loop 1 target setpoint value when ramping
Hex
101D
501D
A03A
Operator Access Setpoint Ramp Rate
Value
Operator Access To Loop 1 Setpoint Ramp Rate
Dec
4126
20510 41020
RW
0
No
Hex
101E
501E
A03C
1
Yes
Summary of Contents for Pro-EC44
Page 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Page 2: ......
Page 6: ......