Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 153
Loop 1 Primary Power Upper limit
Loop 1 Primary Power Upper limit
Dec
4321
20705 41410
RW
10 to 100%
but must be at least 10% above the primary power lower limit.
Hex
10E1
50E1
A1C2
Loop 1 Primary Power Lower Limit
Loop 1 Primary Power Lower Limit
Dec
4322
20706 41412
RW
0 to 90%
but must be at least 10% below the primary power upper limit.
Hex
10E2
50E2
A1C4
Loop 1 Secondary Upper Power limit
Loop 1 Secondary Upper Power limit
Dec
4323
20707 41414
RW
10 to 100%
but must be at least 10% above the secondary power lower limit.
Hex
10E3
50E3
A1C6
Loop 1 Secondary Power Lower limit
Loop 1 Secondary Power Lower limit
Dec
4324
20708 41416
RW
0 to 90%
but must be at least 10% below the primary power upper limit.
Hex
10E4
50E4
A1C8
Loop 1 Pre-Tune Method
Value
Pre-tune type
Dec
4396
20780 41560
RW
0
Standard
Hex
112C
512C
A258
1
Pretune at Value
Loop 1 Pretune at Value
Value To Pre-tune Loop 1
Dec
4399
20783 41566
RW
Valid between the scaled input lower & upper limits
(applies if Pre-Tune Type = Pre-tune at Value)
Hex
112F
512F
A25E
Loop 1 Pretune Set
Value
PID Set Pre-tune Will Optimize
Dec
4397
20781 41562
RW
0
PID Set 1
Hex
112D
512D
A25A
1
PID Set 2
2
PID Set 3
3
PID Set 4
4
PID Set 5
Loop 1 Pretune Cascade Loop
Value
Cascade Loop To Be Pre-Tuned
Dec
4398
20782 41564
RW
0
Slave
(opens cascade - close when finished)
Hex
112E
512E
A25C
1
Master
(tunes master/slave combination)
Loop 1 Pre-Tune Engage/disengage
Value
Pre-Tune Engage/Disengage For Loop 1
Dec
4325
20709 41418
RW
0
Pre-Tune OFF
Hex
10E5
50E5
A1CA
1
Run Pre-Tune
Loop 1 Self-Tune Engage/disengage
Value
Self-Tune Engage/Disengage For Loop 1
Dec
4326
20710 41420
RW
0
Self-Tune OFF
Hex
10E6
50E6
A1CC
1
Self-Tune ON
Loop 1 Loop Alarm Type
Value
Loop Alarm Type For Loop 1
Dec
4327
20711 41422
RW
1
User Defined Time
Hex
10E7
50E7
A1CE
2
Automatic (
2x Integral Time
)
Loop Alarm Time
Loop Alarm Activation Time
Dec
4328
20712 41424
RW
1 to 5999 Seconds after output loop 1 power reaches saturation
Hex
10E8
50E8
A1D0
Loop 1 Primary Power
Loop 1 Primary Power Level
Dec
4329
20713 41426
RO
The current loop 1 primary power level (0 to 100%)
Hex
10E9
50E9
A1D2
Loop 1 Secondary Power
Loop 1 Secondary Power Level
Dec
4330
20714 41428
RO
The current loop 1 secondary power level (0 to 100%)
Hex
10EA
50EA
A1D4