Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 166
Alarm 3 Value
Value At Which Alarm 3 Activates
Dec
6177
22561 45122
RW
Limited by input scaling for alarm types 1 to 4.
Not used for alarms 5, 6 or 7.
0 to 100% for alarms 10 to 12.
Hex
1821
5821
B042
Alarm 3 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6182
22566 45132
RW
Value for Rate of Change Alarm. Alarm 3 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1826
5826
B04C
Alarm 3 Hysteresis
Alarm 3 Hysteresis Value
Dec
6178
22562 45124
RW
Deadband value (on “safe” side of alarm), through which signal
must pass before Alarm 3 deactivates.
Limited by the input scaling span
Hex
1822
5822
B044
Alarm 3 Inhibit Enable/disable
Value
Alarm 3 Power-up/Setpoint Change Inhibit
Dec
6179
22563 45126
RW
0
Disabled
Hex
1823
5823
B046
1
Enabled
Alarm 3 Status
Value
Alarm 3 Status
Dec
6180
22564 45128
RO
0
Inactive
Hex
1824
5824
B048
1
Active
Alarm 3 Inhibit Status
Value
Alarm 3 Inhibit Status
Dec
6181
22565 45130
RO
0
Not Inhibited
Hex
1825
5825
B04A
1
Inhibited
Alarm 3 Label
Main Language Name For Alarm 3 In Status Screen
Dec
6183
22567 45134
RW
8 ASCII characters replacing the title "Alarm 3" in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _
.
Hex
1827
5827
B04E
Alarm 3 Alternate Label
Alternate Language Name For Alarm 3 In Status Screen
Dec
6184
22568 45136
RW
8 ASCII characters replacing the title "Alarm 3" in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _
.
Hex
1828
5828
B050
Alarm 3 Minimum Duration
Alarm 3 Minimum Duration
Dec
6185
22569 45138
RW
Minimum time alarm 3 must be passed its threshold before
activating (deactivation is not affected by this parameter).
From 0 to 9999 secs
Hex
1829
5829
B052
Alarm 4 Input Source
Value
Source
Dec
6191
22575 45150
RW
0
Input 1
Hex
182F
582F
B05E
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Summary of Contents for Pro-EC44