Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 192
Segment Info B (Byte 4 - High)
A/R
(
Floating point
number
)
The meaning of the data contained in
Segment Info B depends on the type of
segment it relates to.
See below
.
Segment Info B (Byte 3)
Segment Info B (Byte 2)
Segment Info B (Byte 1 - Low)
Auto Hold Type Loop 1 High Byte
A/R
A/R
0 = Auto-Hold Off, 1 = Hold above SP, 2 =
Hold below SP,
3 = Hold above and below SP
Auto Hold Type Loop 1 Low Byte
A/R
A/R
Auto Hold Value Loop 1 (Byte 4 -
High)
A/R
(
Floating point
number
)
The distance loop 1 can be way from
setpoint before Auto-Hold activates.
Auto Hold Value Loop 1 (Byte 3)
Auto Hold Value Loop 1 (Byte 2)
Auto Hold Value Loop 1 (Byte 1 -
Low)
Events High Byte
0
0
The status of the five events are defined by
the lowest 5 bits of the low byte. A bit value
of 1 signifies the event is on.
Bit 0 = event 1, bit 1 = event 2, bit 2 =
event 3 bit 3 = event 4 and bit 4 = event 5.
Events Low Byte
A/R
A/R
Segment Info B Loop 2 (Byte 4 -
High)
A/R
(
Floating point
number
)
The meaning of the data contained in
Segment Info B depends on the type of
segment it relates to.
See below
.
(write 0 for single loop profiles)
Segment Info B Loop 2 (Byte 3)
Segment Info B Loop 2 (Byte 2)
Segment Info B Loop 2 (Byte 1 -
Low)
Auto Hold Type Loop 2 High Byte
A/R
A/R
0 = Auto-Hold Off, 1 = Hold above SP, 2 =
Hold below SP,3 - Hold above and below
SP
(write 0 for single loop profiles)
.
Auto Hold Type Loop 2 Low Byte
A/R
A/R
Auto Hold Value Loop 2 (Byte 4 -
High)
A/R
(
Floating point
number
)
The distance loop 2 can be way from
setpoint before Auto-Hold activates.
(write 0 for single loop profiles)
.
Auto Hold Value Loop 2 (Byte 3)
Auto Hold Value Loop 2 (Byte 2)
Auto Hold Value Loop 2 (Byte 1 -
Low)
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Segment Data
The Segment Data is included in the command message when creating, editing or inserting
segments (see above). It is provided in two parts (Segment Info A and B).
The meaning of the data contained in Segment Info A and B depends on the type of segment
it relates to.
Null
is shown for unused data, these data values should be set to zero when
writing the segment data.
Segment Type
Segment
Info
Description
A
B
Ramp Time
Time
Target
setpoint
Ramp to the target setpoint “B” in the time “A”
Ramp Rate
Ramp rate
Target
setpoint
Ramp to the target setpoint “B” at the ramp
rate “A”
Step
Null (0)
Target
setpoint
Step to a target setpoint “B”
Dwell
Dwell time
Null (0)
Stay at the current setpoint for a period of time
“A”
Summary of Contents for Pro-EC44
Page 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Page 2: ......
Page 6: ......