Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 197
Read Quantity Of Registers High Byte
0
0
Read Quantity Of Registers Low Byte
19
13
Write Start Address High Byte
32
20
Write Start Address Low Byte
6
6
Write Quantity Of Registers High Byte
0
0
Write Quantity Of Registers Low Byte
2
2
Byte Count
4
4
Command Code High Byte
82
52
Command Code Low Byte
80
50
Profile Number High Byte
A/R
A/R
Profile number from 0 to 63
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to the Read A Profile Header request as follows:
Read Profile Header - Response (
from instrument
)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
38
26
Profile Name Character 1
A/R
A/R
The ASCII codes equivalent to each of the 16
characters of the profile name, e.g.:
A = 65dec / 0x41, B = 66dec / 0x42 etc.
a = 97dec / 0x61, b = 98dec / 0x62 etc.
Profile Name Character 2
A/R
A/R
Profile Name Character 3
A/R
A/R
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
A/R
A/R
Profile Name Character 10
A/R
A/R
Profile Name Character 11
A/R
A/R
Profile Name Character 12
A/R
A/R
Profile Name Character 13
A/R
A/R
Profile Name Character 14
A/R
A/R
Profile Name Character 15
A/R
A/R
Profile Name Character 16
A/R
A/R
Profile Start Signal High Byte
0
0
0 = No delay, 1 = After delay, 2 = At Time/day
Profile Start Signal Low Byte
A/R
A/R
Summary of Contents for Pro-EC44
Page 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Page 2: ......
Page 6: ......