Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 201
Read a Profile Name
This command requests the name of a specific profile. The instrument responds with the
name of the profile number requested.
Read Profile Name - Request (
to instrument
)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
6
6
Read Quantity Of Registers High Byte
0
0
Read Quantity Of Registers Low Byte
8
8
Write Start Address High Byte
32
20
Write Start Address Low Byte
6
6
Write Quantity Of Registers High Byte
0
0
Write Quantity Of Registers Low Byte
2
2
Byte Count
4
4
Command Code High Byte
80
50
Command Code Low Byte
78
4E
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to the Read Profile Name request as follows:
Read Profile Name - Response (
from instrument
)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
16
10
Profile Name Character 1
A/R
A/R
The ASCII codes equivalent to each of the 16
characters of the profile name, e.g. :
A = 65dec / 0x41, B = 66dec / 0x42 etc.
a = 97dec / 0x61, b = 98dec / 0x62
The space character (32dec / 0x20hex) is used
to fill any unused characters at the end of the
name.
Profile Name Character 2
A/R
A/R
Profile Name Character 3
A/R
A/R
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
A/R
A/R
Profile Name Character 10
A/R
A/R
Profile Name Character 11
A/R
A/R
Summary of Contents for Pro-EC44