Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 61
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
USB MENU SCREENS
USB Mode Unlocking
Enter correct code number to access the USB Menu.
Factory Default value is 10.
Read/Write To USB
Device
Select the required action from: Read Configuration File; Write
Configuration File; Write Recorder Log File. Read Profile Files; Write Profile
Files.
Note:
“Writing” is downloading from the Instrument to the USB
stick. “Reading” is uploading from the USB stick to the
Instrument.
Wr
it
e
Select Profile To
Write
If writing a profile to the USB memory stick, choose a profile to write from
the list provided.
Enter A File Name
Enter an 8-character file name if writing configurations or profiles. A file
extension is automatically added to the end of file name (bct for
configurations or pfl for profiles).
Caution:
Existing files with the same name will be over-written.
Enter A Folder
Name
Recorder logs can contain multiple files. The user enters an 8-character
folder name for these logs. See the Data Recorder section on page 97.
Note:
To prevent existing recordings being over-written, an error
message is shown if the folder name entered already exists.
Writing Profile,
Configuration or
Log
An animated screen is shown the files are being written.
Caution:
Do not disconnect USB device until completed! Data loss or
corruption may result.
Transfer
Successful
Confirmation that the data transfer to the USB stick completed correctly.
Press
R
to continue
Transfer Failure
For write failures, check for adequate disk space on the USB stick.
R
ea
d
Select File
Select the Configuration or Profile file to transfer from the USB stick.
Caution:
Configuration reads overwrite all of the instruments existing
settings with new values.
Reading Profile or
Configuration File
An animated screen is shown while files are being read.
Caution:
Do not remove the memory stick whist this operation is in
progress. Data corruption may result.
Transfer
Successful
Confirmation that the data transfer from the USB stick completed correctly.
Press
R
to continue.
Transfer Failure
For read failures, check the maximum number of profiles and/or segments
is not being exceeded.
Note:
During Data Transfer, normal operation carries on in the background, but
operator access to other screens is not possible. The transfer of a full memory
can take up to 20 minutes. Only begin a transfer when you are certain that
access (e.g. setpoint changes) will not be required.
Summary of Contents for Pro-EC44
Page 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Page 2: ......
Page 6: ......