Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 80
To manually tune a cascade:
1. Select Cascade-Open from the Cascade Control menu, breaking the link between the
master and slave loops.
2. Set the slave controller setpoint manually to the appropriate value for your application.
3.
Tune the slave for relatively fast control (‘proportional only’ is often sufficient).
4. Select Cascade-Closed from the Cascade Control menu to link the master and slave
loops, then tune the master/slave combination.
Summary of Contents for Pro-EC44
Page 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Page 2: ......
Page 6: ......