Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 147
Output 5 AND Alarm Selection
Bit
If Bit = 1, Alarm
n
Is Included in AND Selection
Dec
10133
26517 53034
RW
2
Alarm 1
Hex
2795
6795
CF2A
3
Alarm 2
4
Alarm 3
5
Alarm 4
6
Alarm 5
7
Alarm 6
8
Alarm 7
Output 5 AND Event Selection
Bit
If Bit = 1, Event
n
Is Included in AND Selection
Dec
10134
26518 53036
RW
2
Event 1
Hex
2796
6796
CF2C
3
Event 2
4
Event 3
5
Event 4
6
Event 5
7
Profile Running
8
Profile End
Linear Output 6 Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Linear Output 6 Fitted
Value
Linear Output 6 Fitted
Dec
3016
19400 38800
RO
0
Not fitted
Hex
0BC8
4BC8
9790
1
Fitted
Linear Output 6 Usage
Value
Output 6 Function
Dec
2174
18558 37116
RW
0
Disabled
Hex
087E
487E
90FC
1
Loop 1 Primary Output Power
2
Loop 1 Secondary Output Power
3
Retransmit Loop 1 Actual Setpoint Value
4
Retransmit Input 1 Process Variable Value
5
Loop 2 Primary Output Power
6
Loop 2 Secondary Output Power
7
Retransmit Loop 2 Actual Setpoint Value
8
Retransmit Input 2 Process Variable Value
Linear mA/V DC Output 6 Type
Value
Linear Output 6 Type
Dec
3011
19395 38790
RW
0
0 to 5V DC
Hex
0BC3
4BC3
9786
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Linear Output 6 Level Status
Linear Output % Value
Dec
3014
19398 38796
RO
-2.0% to 102.0% of output nominal range
(
control output will over/under drive by 2%
).
Hex
0BC6
4BC6
978C
Output 6 Retransmit Input 1 Minimum
Value For Loop 1 Retransmit Minimum
Dec
2182
18566 37132
RW
Displayed value at which the retransmission output reaches its
minimum level (e.g. 4mA if type is 4-20mA).
Adjustable from -9999 to 9999.9
Hex
0886
4886
910C