Section BXB-19D-20A
030-100689 Rev. A
R
12
1009IARA
Figure 14. Clean the Air Intake/Exhaust Vents or Louvers
Remove any debris
from all vents
Vents on
left side of
battery box
secure the strap, pass the strap through the left wall tie-down
railing, route the strap around the front then right side of the
battery group, pass the strap through a back wall (or the right
divider wall) railing, then fasten the strap ends/connectors to-
gether and tighten the strap, to snug the batteries up against the
rear and left walls of the compartment. Tighten the strap to re-
move any slack. Examine the strap to verify there is no strap
kinking, binding, or slack.
3.9
Testing the Battery Box Connections
Perform system power-up per company practice or per the in-
structions in the main Boxer cabinet documentation. If trouble
is encountered, verify all battery cable connections are secure
and tight and have good contact or connection.
3.10
Closing and Locking the Cabinets
Upon completion, the installer should close and lock the Boxer
cabinet and the battery box by replacing both compartment
door panels and tightening the cup-washer screws with a can
wrench or 216 tool. The battery box compartment panel op-
tionally can be locked with a padlock (customer supplied) via
a hole provided in the provided padlock flange. Pick up any
tools and materials at the installation site, and clean the site of
any trash or debris.
4.
MAINTENANCE
- CAUTION -
To avoid electrical shock, turn off any DC or AC power feeds
before servicing the unit.
4.1
Replacing the Battery Cable
If the battery cable is not working properly, it can be replaced
by disconnecting it and installing a new one. See Table 2 for or-
dering information. Always disconnect power at the source
before removing the battery cable.
4.2
Inspection and Debris Removal
Westell
r
Boxer
t
battery box components are maintenance-
free, however, at least once every six months, inspect Boxer to
remove any debris from the vents or louvers (Figure 14). This
facilitates proper operation of the cabinet and battery box and
allows unobstructed air flow.
5.
CUSTOMER & TECHNICAL SERVICES
5.1
Customer Service & Technical Assistance
If technical or customer assistance is required, contact Westell
by calling or using one of the following options:
Voice: (800) 377-8766
email:
For additional information about Westell, visit the Westell
World Wide Web site at http://
5.2
Part Numbers
This equipment is identified by a part number
(A90-BXB19-D), which consists of three parts: the equipment
issue letter (A), the assembly type (90), and the model number
(BXB19-D). Each time a change is made to the product which
changes the form, fit, or function of the product, the issue letter
is incremented by one. Be sure to indicate the issue level as well
as the model number when making inquiries about the equip-
ment.
Physical Feature
U.S.
Metric
Height
14 in.
35.60 cm
Width
(including vents)
34.5 in.
87.63 cm
Depth
(excluding lock hardware)
18.60 in.
47.24 cm
Height
(battery compartment)
13.25 in.
33.70 cm
Width
(battery compartment)
18 in.
45.70 cm
Depth
(battery compartment)
18 in.
45.70 cm
Height
(cable compartment)
14 in.
35.60 cm
Width
(cable compartment)
16.50 in.
41.90 cm
Depth
(cable compartment)
18 in.
45.70 cm
Weight
(empty, approx.)
30 lbs.
13.6 kg
Weight Load
(Max.)
250 lbs.
113.4 kg
Outside Operating Temp.
-40
°
to 115
°
F
-40
°
to 46
°
C
Internal cabinet Temp.
-40
°
to 149
°
F
-40
°
to 65
°
C
Humidity
0 to 95% (non-condensing)
Table 1. Boxer Battery Box Physical Specifications
6.
WARRANTY & RETURNS
6.1
Warranty
Westell warrants this product to be defect-free at shipment
time. Westell also warrants this product to be fully functional