background image

Section A90-DCP10X10 

030-101868 Rev A 

 

 

 

 

________________________________________________________________________________

 

Page 2 of 6 

1509IARA 

 

1

. GENERAL DESCRIPTION

 

1.1. 

The  Westell  A90-DCP10X10  Breaker  and  Fuse  Panel 

provides distribution of DC power to equipment.  The panel has 2 
buses,  each  bus  consisting  of  10  pluggable  fuse  or  breaker 
positions.    Alarm  circuits  are  provided  to  indicate  and  extend 
alarm conditions when faults occur. 
 
1.2. 

Input wiring is connected to high current, 2-hole lug input 

terminals located at the rear of the panel.  Each bus has its own 
completely isolated inputs, allowing the distribution of two battery 
voltages through the same panel.   

 

1.3. 

The  power  is  distributed  to  the  load  side  equipment 

through  breakers,  TLS,  TPS  or  TPC  style  fuses.  There  are  10 
positions per group and two groups per panel.  Each position is 
available  for  installer  connection  at  the  rear  of  the  panel.    A 
designation card is provided for keeping records of which position 
is  connected  to  which  equipment  and  what  amperage  is  to  be 
used. 
1.4. 

Alarm circuits are provided to alert service personnel of 

fault conditions. A fuse alarm is generated when a fuse is blown 
or a breaker has toggled into an alarm state. That is, a mid-trip 
breaker  alarms  only  in  the  tripped  position  and  not  in  the  off 
position. However, a non mid-trip breaker will alarm when it is in 

the  off  position.    A  red  alarm  LED

!

on  the  faceplate  will 

illuminate when a fuse or breaker alarm condition is present. As 
well, the green Normal Operation LED 

 will extinguish to signal 

a fuse/breaker alarm or input power failure and the appropriate 
relay  contacts  will  change  states.    These  fuse/breaker  panels 
have common (C), normally open (NO) and normally closed (NC) 
terminals  for  alarms.    Note:  the  use  of  the  alarm  contacts  is 
optional. I

f you do not wish to extend the alarms, you don’t have 

to do anything with the alarm pins. The “Normal” condition of the 
relay  exists  when  the  panel  is  powered  up  without  any  fuse  or 
breaker alarms.  The local alarm LEDs are located on the front of 
the panel as shown in Figure 1.4.1. 

 

LED 

SYMBOL 

SIGNIFICANCE 

GREEN 

 

NORMAL 

OPERATION 

RED 

!

 

BLOWN FUSE 

or TRIPPED 

BREAKER 

           

8

9

10

10

9

8

!

!

BUS A

BUS B

 

Figure 1.4.1

 

 

1.5. 

The 

panels are shipped with universal brackets (1” & 1-

1/4” hole spacing) that will fit both 19" and 23" wide racks and use 
three 1.75" panel spaces.  The panel has two clear plastic shields 
to protect the wiring connections on the back of the panel.  When 
cabling out the top of the panel, use the rear shield.  When cabling 
out of the back of the panel, use the top shield.  

 

2.  APPLICATION

 

2.1. 

The  A90-DCP10X10  Power  Distrirbution  Panel  is 

designed to  be  used  in  the rack  level distribution  of  DC  power.  
They are rack mount panels that provide DC power through two 
busses; each bus has 10 positions. 

 

2.2. 

The A90-DCP10X10 is suitable for installation as part of 

a  Common  Bonding  Network  (CBN).  As  well,  this  product  is 
intended 

for 

restricted 

access 

locations 

in 

Network 

Telecommunications Facilities and OSP. 

 

3.  CIRCUIT DESCRIPTION

 

3.1. 

Power is connected to the panel through 3/8” stud inputs 

(see fig 4.4.1).  There are two sets of input terminations for each 
bus.  These inputs are high current terminations for providing up 
to 600A per bus.  There is a Return (RTN) and Battery (BAT) input 
for each bus. 
 
3.2. 

Distribution  of  current  from  each  bus  is  provided  by 

either breakers, TLS, TPS or TPC style fuses.  Each bus has 10 
pluggable positions.  Each position is made available at the rear 
of the panel via ¼” on 5/8” stud terminals.   
 
3.3.  Fuse/breaker  a

larm  circuitry  provides  1  set  of  form  “C” 

contacts (C, NO and NC) for each bus (Bus A, and Bus B).  In the 
event of a tripped breaker, blown fuse or loss of input power, the 
proper relay will change states, providing a connection between 
the Normally Open “NO” and Common “C” terminals for that bus.  
The normally closed “NC” terminal will open to high impedance.   

 

4.

  

INSTALLATION 

Please read completely before beginning. 
WARNING:

   

Installation  should  only  be  performed  by  an 

experienced Installer familiar with DC power distribution systems. 

 

This  product  must  be  installed  within  a  RESTRICTED 
ACCESS  LOCATION  where  access  is  through  the  use  of  a 
tool,  lock  and  key  or  other  means  of  security,  and  is 
controlled by the authority responsible for the location.  This 
product  must  be  installed  and  maintained  by  TRAINED 
SERVICE PERSONNEL ONLY. 

 
4.1. 

Unpack  and  inspect  the  Panel  for  possible  damage 

incurred  during  shipping.    If  damage  is  found,  file  a  claim 
immediately with the carrier, and notify Customer Service. 
 
4.2. 

Once the panel is unpacked, verify that there are two sets of 

mounting brackets.  One set is for 19” racks, and the other for 23” 
racks.  The brackets will fit both 1

” and 1-1/4” hole spacing applications.  

The brackets can be mounted so the panel can be installed for a flush 
mounting or offset positions.  Adjust the position and orientation of the 
correct mounting brackets on the fuse panel, such that it will fit the rack 
you wish to mount the panel in. 

 

Reviews: