background image

Section BXM‐05V‐20A

030‐101643 Rev. B

R

4

1205IARB

2.2

Interior Features

The features located inside Boxer  are described hereunder.

2.2.1

Door Sensor Switch

A door sensor switch for door alarm reporting purposes is lo­
cated at the top, left, front corner of the cabinet (Figure 7).
This switch is factory‐prewired to a cable stub. Connect the
wires as needed to the field‐installed equipment. To temporari­
ly disable the sensor, pull out the cylindrical door switch
actuator until it clicks. To re‐activate the sensor, either gently
push the actuator back in until a click is heard, or simply close
the cabinet door.

2.2.2

Internal 19” Rack Channels

Two removable/adjustable rack channels (see Figure 8 or
Figure 13) inside the cabinet provide 19” relay rack mounting
for equipment that is to be mounted in the cabinet. With each
rack channel in the forward‐most position, the distance
between the inside of the closed front door and the channel's
front face is approximately 3.75” (equipment projection), and
the distance from the channel's rear face to the cabinet's interi­
or mesh backboard is approximately 12.5”. Three rack channel
positions are available (see Figure 13), each 1” apart, if one or
two additional inches of equipment depth is needed at either
the front or back of the channel. Each rack channel also con­
tains predrilled holes, with standard hole spacings (either 1”,
1.75”, or 2” rack hole patterns), to mount customer‐supplied
equipment in the cabinet. Network equipment up to 5 Rack
Units (5 RUs: 5 x 1.75 = 8.75”) high can be mounted vertically
on the internal rack inside the cabinet, either as a single piece
or multiple pieces of equipment.

‐ EXTRA RU NOTE ‐

An extra rack unit of equipment mounting space is available at
both the left and right sides of the cabinet; however, these RUs
have limited front access (partially obstructed).

2.2.3

Grounding and Bonding Center

Boxer's grounding and bonding center is located on the bottom
interior surface of the cabinet, close to the front door. A
ground plate is provided that contains five sets of ground posts
and one copper ground lug, for cable and chassis/earth ground.
Bond equipment/cables to the ground posts per company prac­
tice, and connect a #6 AWG chassis or earth ground wire to the
ground lug. An Electro‐Static Discharge (ESD) wrist‐strap
jack is also located on the ground plate.

3.

INSTALLATION

Use and follow local codes and company practices to install the
Westell

r

 Boxer

t

 cabinet. If none exist, use the instructions

contained herein. Installation consists of:

S

inspecting the unit for possible shipping damages,

S

following proper safety precautions,

S

reviewing pre‐mounting considerations, such as selecting
the mounting type and location, and preparing the mount­
ing site,

S

gathering all tools, materials, and equipment,

Figure 8.

Internal Rack Space for Equipment

5 RUs of rack space (1 RU = 1.75” RU)

Upper and

lower rack

channels,

with 1”,

1.75” or 2”

rack hole

patterns

 

1RU

1RU 1RU

1RU

1RU

Extra Space*

* An additional RU is available at the left side which has limited front access (partially‐obstructed)

 

S

removing knock‐outs where holes are needed,

S

mounting the cabinet,

S

making ground connections,

S

mounting customer‐supplied equipment inside the cabi­
net,

S

making communication cable connections,

S

making any needed alarm connections,

S

optioning the installed equipment and placing it in service,
and

S

performing cabinet housekeeping, and closing and lock­
ing the cabinet.

The following paragraphs provide detailed instructions for
performing these procedures.

3.1

Inspecting the Equipment

‐ INSPECTION NOTE ‐

Visually inspect the unit for damages prior to installation. If the
equipment has been damaged in transit, immediately report the
extent of the damage to the transportation company and to West­
ell (see Part 5 for telephone number).

‐ DESICCANT NOTE ‐

To prevent condensation during shipment and storage, Westell
includes a desiccant pack within the Boxer cabinet. Once the
electronic equipment is installed and turned‐up, the internal
power dissipation reduces the likelihood of condensation within
the cabinet. However, follow company practices for desiccant
maintenance procedures to prevent internal condensation.

Summary of Contents for Boxer BXM05V19-NMT

Page 1: ... NMT Boxer cabinet also may be commonly referred to as the Boxer 5 or cabinet 1 2 Document Status Whenever this practice is updated the reason will be stated in this paragraph Revision B updates the Boxer part number and updates Paragraph 1 3 1 3 Product Purpose and Description Boxer is a compact NEMA 4 weather tight outdoor cabinet that houses and protects a wide range of electronic equipment Up ...

Page 2: ...ottom accept a variety of cable conduit and connector sizes and types six 1 two 2 S Door security via a locking hex cup washer bolt which also accepts a padlock S Door sensor alarm switch for optional alarm security S Included mounting brackets allow pole H frame wall or square post mounting S Optional battery backup box available knock out hole patterns match in both units S Bagged parts self tap...

Page 3: ... has three mounting holes or slots The center hole of the top bracket is a keyhole for easy one person cabin et self leveling mounting Use mounting fasteners with a diameter of up to 3 8 The vertical distance between the top and bottom mounting bracket hole centers is 25 18 see Figure 5 Quantity Description 2 2 5 knock out for 2 conduit 6 1 125 knock out for 3 4 conduit Table 1 Knock out Sizes and...

Page 4: ... A ground plate is provided that contains five sets of ground posts and one copper ground lug for cable and chassis earth ground Bond equipment cables to the ground posts per company prac tice and connect a 6 AWG chassis or earth ground wire to the ground lug An Electro Static Discharge ESD wrist strap jack is also located on the ground plate 3 INSTALLATION Use and follow local codes and company p...

Page 5: ...stance from the cable entry point or from upstream or downstream equipment 3 4 Gathering all Tools and Equipment The following tools and supplies not provided are required to mount the Boxer cabinet Door Opening Locking Tools V 7 16 can wrench or 216 tool V Padlock optional Knock Out Removal Tools V Hammer V Punch V Pliers Cabinet Mounting Tools Equipment and Hardware V Tape measure V Marking uten...

Page 6: ...nt of the mount ing to allow the door to open see Figure 4 and at the sides in the event of any multiple installations 2 Remove knock outs See the steps in Paragraph 3 5 Re moving the Knock outs to remove the knock outs where any cable access holes or holes for mounting the optional battery box are desired 3 Prepare the mounting hardware Bring the appropriate mounting hardware to the installation ...

Page 7: ...Drill appropriately sized pilot holes slightly smaller than the width and depth of the bolts at the marked loca tions Do not drill the holes too large 10 Install bottom mounting bolts Insert and drive all bottom bolts completely in to their final seated position Finish the installation by verifying all bolts are firm and snug 11 Determine next step or close up cabinet and clean the site Repeat Ste...

Page 8: ...of the cabinet 4 Verify each piece of equipment does not exceed the cabi net s interior width or depth 5 Determine the best mounting location for each piece of equipment for maximum capacity 6 Determine adjust the rack channel depth optional If the factory installed rack channels are not at the proper equip ment projection depth adjust the channels at this time Remove the nuts that secure each cha...

Page 9: ...assembly and return it to Westell for service then replace it To remove and replace the door alarm switch assembly proceed with the following instructions 1 Open the cabinet Open the large main cabinet door 2 Remove door sensor assembly mounting screws Remove the nuts that attach the door alarm sensor to the threaded posts in the top right inside corner of the open cabinet 3 Partially pull out doo...

Page 10: ...cycle and dispose of the products per your company prac tice per local recycling programs and local codes and per state statutes 7 SPECIFICATIONS 7 1 Physical Specifications The Boxert physical specifications are shown in Table 2 7 2 Regulatory Agency Specifications The Boxer cabinet is designed to meet the following regulatory safety or environmental specifications or requirements S NEMA 4 compli...

Page 11: ...Section BXM 05V 20A 030 101643 Rev B R 11 1205IARB Figure 15 Knock out Locations and Sizes 1 13 KNOCK OUT 6 PLCS ...

Page 12: ...Section BXM 05V 20A 030 101643 Rev B R 12 1205IARB Figure 16 Front View Door Open 25 2 27 7 0 625 dia 7 Depth door closed 18 23 1 5 1 5 0 375 dia 0 375 dia ...

Reviews: