background image

 

_____________________________________________________________________________________

   

 

 

 

 

 

 

 

 

 

 

  

  

 

4

Mounting Options

 

Figure 4.2.1 

 
 
4.3.  

Mount the fuse panel in the required 

position on the equipment rack using #12-24 
thread forming rack mounting screws with 
external tooth lock washers that are provided 
with the panel.   

 
WARNING:

 For safety reasons all wiring 

should be done with power source removed. 

 
4.4.

  Remove the distribution fuse or breaker 

feeding the input cables that are to be 
connected to the new panel.  Note this panel 
can handle a maximum of 125 Amps per 
input.  Please do not fuse/breaker the input 
cables at more than 150 Amps each.  Using 
input cables specified by the Job Engineer, 
hook up the battery input cables to the input 
blocks on the back of the fuse panel (“BAT 
IN” & “RTN IN” for each input).  Each input 
terminal uses a two hole compression lug 
(1/4” on 5/8” centers, torque to 3 ft-lbs).  See 
Figure 4.5.1. 

 
4.5.

  Battery outputs (“BAT OUT” & “RTN 

OUT”) for each fuse position are also 
accessible through ¼” stud terminal blocks at 
the rear of the panel.  Each fuse position is 
numbered on the face plate and that circuits 
output is available at the back of the panel 
with the same number.  Note that each return 

is isolated from the chassis frame and 
isolated from all other returns.  See Figure 
3.1.1.

 

 
Note:

 For this high current panel, a two hole 

lug must be used on all stud blocks (input and 
output, battery and return) for the fuse panel 
to function properly.   

 
4.6.

 Each fuse position has a common (C), 

normally open (NO) and normally closed (NC) 
set of contacts for extending alarms.  (See 
figure 4.6.1 for the location and layout of the 
alarm relay contacts).  Wire wrap the alarm 
connections as per your alarm systems 
requirements.  For example; to achieve a 
“ground alarm extension”, connect a ground 
supply to the common (C) contact and 
connect the alarm signal wire to the normally 
open (NO) contact.  In an alarm state a 
“ground” will be sent out from the panel. 

COM

NC

NO

1

2

3

4

CHASSIS

GND

BAT IN

BAT OUT

ALARMS

 

Figure 4.6.1

 

 
Note:

 To protect the alarm wiring and 

circuitry, the current will be limited through the 
alarm contacts to 1A by a self-resetting over 
current device (1Amp P.T.C.).  See the 
attached schematic (drawing 1009-10).  

 
4.7

  Chassis Grounding; for safety reasons, 

the chassis should be electrically connected 
to the rack ground.  From step 4.3, the panel 
should already be bonded to the rack via the 
#12-24 thread forming rack screws and 
outside tooth lock washers used to pierce the 
paint (this hardware must be used to pierce 
paint on the panel and the rack).  In addition 
to grounding via the mounting brackets, it is 
recommended that the chassis be further 
grounded using a separate ground bonding 

Summary of Contents for NPTFD1009

Page 1: ...ive 4 isolated TLS fuse positions TFD style holder 125 Amps each 500 Amps per panel TFD fuse holder accepts TLS Fuses up to 125 Amps or TPS Fuses up to 70 Amps Normal and Fuse Alarm LEDs for each fuse...

Page 2: ...is present a red Fuse Alarm LED will illuminate As well the green Normal Operation LED 9 will extinguish to signal a fuse alarm or input power failure and the appropriate relay contacts will change st...

Page 3: ...l be lit provided there is no power failure Figure 1 4 1 shows the alarm LED layout 3 4 There is one set of dry Form C contacts to extend alarms for each fuse position In the event of a Fuse Alarm or...

Page 4: ...solated from all other returns See Figure 3 1 1 Note For this high current panel a two hole lug must be used on all stud blocks input and output battery and return for the fuse panel to function prope...

Page 5: ...l Operation LEDs 9 for each input that has been connected and have no red Fuse Alarm LEDs illuminated 4 9 Install fuses in each of the TFD cartridges as required Unless otherwise specified be sure to...

Page 6: ...ure 40 to 131 F 5 14 Color Off White 5 15 Relay current 1Amp 58Vdc max We recommend that you size fuses such that they do not run at more than 70 of their rating Thus a 70A fuse should not be run at m...

Page 7: ...rning the sale of the product Any attempt to repair or modify the equipment by anyone other than an authorized Westell representative will void the warranty 7 2 Westell will repair or replace any defe...

Page 8: ...___________________ 8 COM NC NO 1 2 3 4 1 2 3 4 CHASSIS GND BAT IN RTN IN RTN OUT BAT OUT RTN OUT BAT OUT BAT IN RTN IN RTN OUT BAT OUT BAT IN RTN IN RTN OUT BAT OUT BAT IN RTN IN 4 3 2 1 1 2 3 4 ALAR...

Page 9: ..._____________________________________________________________________________________ 9 Noran Tel 5 OFFSET MOUNTING FLUSH MOUNTING 0 2500 4 2700...

Page 10: ..._____________________________________________________________________________________ 10...

Reviews: