Multidrop application

Follow the steps below to get the unit up and running in a simple application.  

TX

RX

TX

RX

TX

RX

TX

RX

TX

RX

TX

RX

TX

RX

TX

RX

CH 2

CH 1

PROFIBUS DP

CH 2

CH 1

PROFIBUS DP

CH 2

CH 1

PROFIBUS DP

CH 2

CH 1

PROFIBUS DP

Master 

Slave

Slave

Slave

Prepare the PROFIBUS units

…  

Configure PROFIBUS DP network, with master and slaves. Check that it is running 
correctly with the electrical PROFIBUS DP network.

Prepare the fibre optical network

…  

Multidrop, mid units (CH 1 & CH 2). Set switch S2:2 set to ON and all others to OFF.

…  

Multidrop, end units (CH 1 only). All switches should be set to OFF.

…  

Connect the fibre links between the units.

…  

Connect the power supply to all units.
• The Fibre links should be in operation, indicated by active CH 1 and CH 2 LED’s.

…  

Connect each of the PROFIBUS DP slaves to the PROFIBUS DP port of the 
corresponding ODW-612.

…  

Connect PROFIBUS DP master to the PROFIBUS DP port of one ODW-612
• The PROFIBUS DP will be in operation and the data rate should have been 
  identified, indicated by BA LED.

…  The Multidrop application is up and running.

Note!

 ODW-611 can be used as end units.

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr

Summary of Contents for ODW-600 Series

Page 1: ...peater line and redundant ring www westermo com Westermo Teleindustri AB User Guide 6650 2212 ODW 612 Fibre Optic Modem AUDIN 8 avenue de la malle 51370 Saint Brice Courcelles Tel 03 26 04 20 21 Fax 0...

Page 2: ...r contents of this document Westermo reserves the right to revise this document or withdraw it at any time without prior notice Under no circumstances shall Westermo be responsible for any loss of dat...

Page 3: ...optical fibre port or any connected fibre Care recommendations Follow the care recommendations below to maintain full operation of the unit and to fulfil the warranty obligations This unit must not be...

Page 4: ...e protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used...

Page 5: ...conformity No Title Issue EN 50121 4 Railway applications Electromagnetic compatibility Emission and immunity of the signalling and telecommunications apparatus 2006 EN 55022 Information technology eq...

Page 6: ...50 Hz EN 61000 4 16 Signal ports 100 V 50 Hz line to earth Mains freq 50 Hz SS 436 15 03 Signal ports 250 V 50 Hz line to line Radiated emission EN 55022 Enclosure Class B FCC part 15 Class A Conduct...

Page 7: ...a frame Retiming ensures the correct PROFIBUS DP signal format 9 position D sub PROFIBUS DP connector Data rate up to 12 Mbit s Automatic data rate detection and retiming Redundant ring alternatively...

Page 8: ...depends on selected fibre transceiver and fibre type Distances up to 80 km 50 miles are available Data rate up to 12 Mbit s ODW 612 converts PROFIBUS DP data using data rates from 9 600 bit s up to 1...

Page 9: ...ceives PROFIBUS DP data from the Slave UnitS converts slave data and transfers the slave frame via ring A The repeating of transferred frames is stopped until this transferred slave frame has returned...

Page 10: ...ed in one direction via CH 1 only Data received from one ODW 612 optical fibre port will be repeated through the other optical fibre port and it will also convert the frame to PROFIBUS DP data and sen...

Page 11: ...ate permanently over a wide input range and provided with two independent inputs allowing redundancy should either supply fail 9 position D sub PROFIBUS DP connector The pin assignment for the connect...

Page 12: ...ll system delays differ see below Redundant ring one data exchange The data exchange between PROFIBUS DP master and slave via ODW 612 fibre optic link will run one direction through all units of the r...

Page 13: ...nt ring one data exchange between master and one slave One PROFIBUS DP master and 11 slaves with data rate 1 5 Mbit s 12 ODW 612 units with a total fibre length of 40 km A data exchange between master...

Page 14: ...t Yes Isolation to PROFIBUS DP and Status port Connection Detachable screw terminal Connector size 0 2 2 5 mm2 AWG 24 12 Shielded cable Not required Status Port type Signal relay changeover contacts R...

Page 15: ...itter Output optical power min max 5 0 dBm 5 0 dBm 15 8 dBm 20 14 dBm Receiver Input sensitivity 34 dBm max 34 dBm max 31 dBm max 31 dBm max Receiver Input optical power Maximum 5 dBm min 3 dBm min 8...

Page 16: ...NO Contact with C when link is in operation No 2 C Common No 3 NC Open no con tact with C when fibre link is in operation 4 position marking Description No 1 Voltage No 2 Voltage A No 3 Voltage B 9 p...

Page 17: ...ion Data can be transmitted OFF Fibre link at port CH 1 out of opera tion DPR Receive PROFIBUS DP Flash Receive data on the electrical PROFIBUS DP port Data will be transmitted to the fibre link if it...

Page 18: ...mid unit Both optical fibre ports CH 1 CH 2 ON 1 2 3 4 5 6 7 8 Redundant ring application ON 1 2 3 4 5 6 7 8 65535 tbit interruption in receiving frames until inactive BA ON 1 2 3 4 5 6 7 8 10 seconds...

Page 19: ...ntified S1 No extended retry limit ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 7 faulty frame before data rate is seen as unidentified S1 No extended retry limit ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 8 faul...

Page 20: ...ture range and service life Removal Press down the black support at the top of the unit See figure Mounting This unit should be mounted on 35 mm DIN rail which is horizontally mounted inside an appara...

Page 21: ...ON and all others to OFF at all units Connect the fibre links between the units Connect the power supply to all units The Fibre links should be in operation indicated by active CH 1 and CH 2 LED s Con...

Page 22: ...d all others to OFF Multidrop end units CH 1 only All switches should be set to OFF Connect the fibre links between the units Connect the power supply to all units The Fibre links should be in operati...

Page 23: ...ferred PROFIBUS DP frames is long it may be necessary to allow a longer time of interruption in receiving frames using DIP switches If disturbances in the electrical PROFIBUS DP network result in miss...

Page 24: ...an Road Park Gate Southampton SO31 7GA Phone 44 0 1489 580 585 Fax 44 0 1489 580586 E Mail sales westermo co uk Westermo Data Communications GmbH Goethestra e 67 68753 Wagh usel Tel 49 0 7254 95400 0...

Reviews: