21
6651-22631
Prepare the master units
…
Configure network, with master and slaves. Check that it is running correctly with the
electrical serial network.
Prepare the fibre optical network.
…
Redundant ring. Set switch S2:1 and 3 to ON and all others to OFF, at all units.
(If the status interface should be local, set S2:6 to ON)
…
Set present data rate with S1.
…
Connect the fibre links between the units.
…
Connect the power supply to all units.
• The Fibre links should be in operation, indicated by active CH 1 and CH 2 LED’s.
…
Connect each of the slaves to the port of corresponding ODW-620-F2.
…
Connect the master to the port of one ODW-620-F2.
…
The Redundant ring application is up and running.
Start up guide, redundant ring application
Follow the steps below to get the unit up and running in a simple application.
Ring A
Ring B
TX
RX
TX RX
TX
RX
TX RX
TX
RX
TX RX
TX
RX
TX RX
CH 2
CH 1
CH 2
CH 1
CH 2
CH 1
CH 2
CH 1
PLC
Slave
PLC
Master
PLC
Slave
PLC
Slave
Ring A
Ring B
Ring A
Ring B
Ring A
Ring B
Ring A
Ring B