WRD
–
Leonardo Datalogger
Quick Installation Guide
EN
*Ubat GE Start 1500 = ---
for Leonardo Off-Grid 1kW/1500/24 GE (cod. 014392)
*Ubat GE Start 3000 = 46V
for Leonardo Off-Grid 4kW/5000/48 GE (cod.013967)
*Ubat GE Start 3000 = 46V
for Leonardo Off-Grid 4kW/5000/48 GE (cod.014087)
*Ubat GE Start 3000 = 46V
for Leonardo Off-Grid 8kW/8000/48 GE (cod.014939)
* in three-phase configurations multiply these values x 2
Ubat GE Hist = +10V
Press and hold
(ENTER) to confirm.
7.
Press and hold the
(ESC) key to move to the
7.0 SYSTEM
menu. Press and hold
(ENTER) to enter
parameter edit mode. Press
(ENTER) again and use the
(DOWN) e
(UP) keys to select / set the
battery:
Batt.Type: 2-Pb Seal/Gel 57.60V@25°C
B.Capacity: ..inserire il valore degli Ah della Batteria installata
OFF disch.: 40%
ON disch.: 85%
OFF charge: 100%
ON charge: 100%
WRM Pg.Load: OnSurPlus
WRM LB.Load: 44.48V
Press and hold
(ENTER) to confirm.