WRD
–
Leonardo Datalogger
Quick Installation Guide
EN
2.
From Home, press and hold the two arrows
(DOWN)
(UP) simultaneously to enter the setup menu.
3.
Scroll to menu
7.5 VARIOUS
press and hold
(ENTER),
Scroll to “Advanced Setup” press
(ENTER), then
press the
(UP) key and hold down the
(UP) key.
4.
In menu
8.0 WBUS CONFIG.
use the 'AutoConf.' command: keep pressed
(ENTER) to enter the parameter edit
mode. Press
(ENTER) again. Press the
(UP)key, "RUN" appears in the value field. By keeping the
(UP)
key pressed, the self-configuration of all the peripherals connected to the device is performed. Press and hold
(ENTER) to confirm.
5.
In menu
8.2 WRM30
set:
MPPT = A
–
B
for Leonardo Off-Grid 4kW/3000/48 GE Py (cod. 016274)
for Leonardo Off-Grid 4kW/5000/48 GE Py (cod.016445)
MPPT= A//B
for Leonardo Off-Grid 8kW/8000/48 GE Py (cod.017599)
Press and hold
(ENTER) to confirm.
6.
Navigate to menu
8.3 W-INVERTER
. Press and hold
(ENTER) to enter parameter edit mode. Press
(ENTER)
again. Using the
(DOWN) and
(UP) keys to select and set:
System Type = 3-GE-LI
*GE Power 3000 = 2200W
for Leonardo Off-Grid 4kW/3000/48 GE Py (cod. 016274)
*GE Power 5000 = 3600W
for Leonardo Off-Grid 4kW/5000/48 GE Py (cod.016445)
*GE Power 8000 = 5800W
for Leonardo Off-Grid 8kW/8000/48 GE Py (cod.017599)
* in three-phase configurations multiply these values x 2
MeterPort = -
AC Charger = -
WRM Feed-In = -
Web SetPoint = -
TA Position = -
Max Pw Grid = -
Ubat GE Start = ---
Ubat GE Hist = +8V