Recommended Rack
Configurations
4. Installation
4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B)
4.1
PDU Mounting Bracket Installation (KIT-MBVPT-1B)
The installation of PDU mounting bracket kit (KIT-MBVPT-1B) for the AFCO, TRIPPLITE, and CRENLO racks
extends the PDUs farther back in the rack to allow for more room for the CMA and enclosure.
Note:
For recommended vertical rack rail settings, see:
Table 31:
Procedure Info
Required Tools
Required Parts
# of People
Required
•
Torx T15 Screwdriver
•
Two Flat Brackets
•
Two Right-Angle Brackets
•
Two Backer Plates
•
M6 x 16 Hex Cap Screws
•
M6 Fender Washers
•
M6 Hex Nut with Nylon Lock
1
Step 1 :
Install the bottom side bracket using the provided hardware.
a.
Locate the two screw holes at the bottom of the back side of the PDU.
b.
Align the flat bracket with the two bottom PDU screw holes as shown.
Figure 6:
Flat Bracket (bottom)
c.
Secure the flat bracket to the PDU by using the screws provided in the PDU mounting kit as
shown in the image below.
19