WM038 EasyCube 105 v1 EN Feb 2021

 

10 

LIFTING & HANDLING 

 

IMPORTANT: Always prepare a Lifting Plan/Risk Assessment. 

By  Forklift / Tele-handler 

 

Each EASYCUBE is fitted with forklift pockets which are designed to allow the 

EASYCUBE to be raised by a forklift/tele-handler. The EASYCUBE can be lifted 

from both the front and the back.  

 

It is important that the total gross weight of the EASYCUBE is not more than 

half (50%) of the forklift’s maximum SWL. Ensure that the forklift’s forks are 

set to the correct width for the EASYCUBE’s fork pockets 

WARNING 

Do not allow anyone under the raised load at any time or for any 

reason.

 

 

Positioning 

 

You should make sure that both supplying vehicle and receiving vehicle have 

safe and easy access to the EASYCUBE 

 

The position should be selected where the unit  will be protected from 

accidental impact 

 

Be aware of the location of underground services, such as drains, and manhole 

covers 

 

You must also consider the ground surface and make sure it can support the 

weight of the EASYCUBE, its contents when full and any stored equipment such 

as pumps, without the risk of subsidence. It should be positioned on smooth 

and level ground  

 

Allow for access that may be required by the emergency services should it 

become necessary 

 

 

Summary of Contents for ECW105

Page 1: ...TRANSPORTABLE TANK ECW105 01 4710 ...

Page 2: ...ACCESS AND SECURITY 8 CABINET OVERVIEW 9 LIFTING HANDLING 10 FILLING THE EASYCUBE 11 DISPENSING FUEL 11 TRANSPORTING 11 STACKING 11 MAINTENANCE AND SERVICE SCHEDULE 12 STATUTORY INSPECTION AND MAINTENANCE 13 INNER TANK REMOVAL 15 ENVIRONMENTAL RESPONSIBILITY 16 TROUBLE SHOOTING 17 WARRANTY 18 ...

Page 3: ...manual is governed by law and is subject to change without prior notice Great care has been taken to ensure that the information is correct at the time of publication However it is the owner s user s sole responsibility to ensure that they and the tank fully comply with all legal requirements Western Global cannot and will not accept any liability for any inaccuracy or incorrectly stated legal req...

Page 4: ...fuel on the highway road There is no need to drain empty the tank before transporting The EASYCUBE can be used as an auxiliary fuel tank feeding generators etc and for refuelling other equipment via a dedicated fuel pump All pipe work and pump systems are stored beneath a secure lockable lid To aid both transporting and handling the EASYCUBE is fitted with forklift pockets Containment Bund has a c...

Page 5: ...nk is supplied with a unique identification numbers 1 UN IBC Serial Number 1 UN IBC Serial Number The UN IBC Plate is located on the front external of the tank Record your serial number here UN IBC Data plate Serial Number Plant Number Optional customer plant number ...

Page 6: ...apacity Litres US Gallon Imp Gallon Nominal Safe Fill Nominal Safe Fill Nominal Safe Fill EASYCUBE 105 107 102 28 27 24 22 Model Weight KG LBS TARE GROSS TARE GROSS EASYCUBE 105 66 168 146 370 Model Dimension Metric mm Imperial Inch L W H L W H EASYCUBE 105 680 600 1025 26 8 23 6 40 4 ...

Page 7: ...WM038 EasyCube 105 v1 EN Feb 2021 5 SAFETY Before using this equipment and to avoid personal injury carefully read and understand these instructions ...

Page 8: ...loose jewellery or clothing that may get in the way or become trapped in the mechanism Inspect the unit before use if there is any doubt about its condition DO NOT USE IT Do not smoke No naked flames near tank Please follow all necessary Transportation of Dangerous Goods act regulations and codes National and Regional Fire Safety Codes and other Installation Codes as applicable in your region coun...

Page 9: ...l of its stated Nominal capacity Safe practice The storage transportation and dispensing of Flammable Combustible fluids is governed by law and it is the user operator who has sole responsibility to ensure that any such rules and regulations are abided by Venting Each unit has a vent fill cap fitted on the top of the inner tank IMPORTANT Do not operate the unit if this vent fill cap is damaged or ...

Page 10: ...duty steel care should be taken when opening or closing Ensure the lid safety catch is engaged Security The EASYCUBE is fitted with a pump to enable the supply of Flammable Combustible fluids All the connections are housed behind the cabinet hatch which can be locked using a suitable security padlock The cabinet hatch should be kept closed when the EASYCUBE is not being used to protect the fitting...

Page 11: ...WM038 EasyCube 105 v1 EN Feb 2021 9 CABINET OVERVIEW 1 Vent Fill Cap 2 Inner Tank 3 1 Hand Pump 4 1 Deliver Hose 5 Ball Valve to 1 Reducing nipple Nipple 6 feed Block ...

Page 12: ...ork pockets WARNING Do not allow anyone under the raised load at any time or for any reason Positioning You should make sure that both supplying vehicle and receiving vehicle have safe and easy access to the EASYCUBE The position should be selected where the unit will be protected from accidental impact Be aware of the location of underground services such as drains and manhole covers You must als...

Page 13: ... nozzle unattended during the filling process Observe the fuel level gauge for an indication of tank capacity then once filled replace the filler cap and clean up any spills DISPENSING FUEL There are two options available for dispensing supplying fuel Either manually via a fuel pump and nozzle or by direct coupling to the equipment such as a generator NOTE Direct coupling cannot be used in conjunc...

Page 14: ...nce Comments General Housekeeping V P Check site and tank Remove debris etc Firefighting media if fitted V P V Check in place and unused P Test pressure and function Signage V R Check damage and wear Tank Ball valves P P Check operation Vents V V Visual checks for leaks and damage Containment P Check for water or product Tank earthing V P V Visual check OK P Test continuity ...

Page 15: ...20 To retain the UN IBC approval it is required that the owner of the EASYCUBE carries out regular inspections and ensures that a record of each inspection is kept Where fault is found the unit MUST be removed from service until the fault is rectified and the unit is retested successfully Every 2 years External inspection Function of all services equipment Leak test Every 5 years Internal inspecti...

Page 16: ... of the IBC at least until the next inspection or test The report shall include the results of the inspection and test and shall identify the party performing the inspection and test Owner Date of manufacture Model Serial Number Plant Number Capacity Date 2 5 or 5 Year Pass or Fail Comments Inspectors Name Signature ...

Page 17: ... Follow local Health and Safety rules when carrying out this operation IMPORTANT Ensure the tank is empty before lifting 1 Remove the hand pump 1 If fitted and disconnect the feed pipe at position marked 2 2 Remove the rear securing nuts and bolts 3 Remove the front securing nuts and bolts The inner tank can then be lifted out of the containment ...

Page 18: ... will contain all the necessary items to retain and remove such a spill DO NOT hose the area down or use any detergents DO NOT allow the fuel to enter drains or watercourses Spills must be reported to your local Authority All material used to retain and remove a spill should be bagged and collected by a registered carrier Containment The EASYCUBE containment area safeguards against any spill exiti...

Page 19: ... If a problem is difficult to solve even after having read through this trouble shooting section please call your local Western Global distributor or dealer PROBLEM CAUSE SOLUTION Fuel in containment Loose fitting Tighten fitting Leaking Coupler Replace coupler Over filling Do not fill past 95 of the nominal capacity Water in containment Lid left open to weather Keep lid closed ...

Page 20: ...ation or shipment costs to and from the manufacturer or their recognised agents for repair or assessment against a warranty claim on any product or component Materials and or labour costs to renew repair or replace components due to normal wear and tear Faults arising from the use of non standard or additional parts or any consequential damage or wear caused by the fittingor use of such parts IMPO...

Page 21: ......

Reviews: