29
MENU 8.1
WBM.SETUP:
not present
List displayed:
Settable values and description:
Value:
Device not present.
MENU 8.1
WBM SETUP:
Batt.Type:
Pb Seal/
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B.Capacity:
200Ah
|
|
OFF disch.#1:
↓
25%
|
|
ON disch.#1:
↑
40%
|
|
OFF charge#2:
↑
100%
|
|
ON charge#2:
↓
90%
|
|
UPDATE FW:
---
List displayed:
Settable values and description:
Value:
RUN
: *CAUTION* starts the procedure to update the
firmware in the WBM device. The firmware update
file must be present in the uSD card.
no-smart battery
Pb Flood 14.80@25°C / 29.60@25°C / 59.20@25°C :
Setting to operate with battery type
Pb Flood.
Pb Seal/Gel 14.40@25°C/ 28.80@25°C / 57.60@25°C :
Setting to operate with battery type
Pb Seal or Gel.
LiFePO4
<
14.00..14.70V
>
fixed
<
28.00..29.40V
>
fixed
<
56.00..58.80V
>
fixed:
Setting
to
operate
with
battery
type
Lithium with integrated BMS.
smart battery
4
1 - LG Chem RESU 57.60 fixed:
LG CHEM RESU smart battery setting.
2 - PYLONTECH 54.00 fixed:
Pylontech smart battery setting.
3 - MIDAC 59.00 fixed:
MIDAC smart battery setting.
<
10..2000Ah
>
Battery bank capacity,for calculating SoC.
<
0%..ON disch
> below this threshold, the ALARM 1 output
is actived. Discharging OFF.
<
OFF disch..100%
> above this threshold, the ALARM 1
output is deactived. Discharging ON
<
ON charge..100%
> above this threshold, the ALARM 2
output is deactived. Charging OFF.
2
<
0%..ON charge
> below this threshold, the ALARM 2
output is actived. Charging ON.