I.L.
41-103H
ENERGY REQUIREMENTS
TYPE C0-2 RELAY
60
HERTZ VOLT AMPERES** (Xll FOR
50
HZ)
AT
AT
3
TIMES
AT
10
TIMES
AT
20
TIMES
CONTINUOUS
ONE SECOND
POWER
TAP VALUE
TAP VALUE
TAP VALUE
TAP VALUE
0AMPERE
RATING
RATING*
FACTOR
CURRENT
CURRENT
CURRENT
CURRENT
RANGE
TAP
(AMPERES)
(AMPERES)
ANGLE<!>
(Ll =
0.86)
(Ll =
0.88)
(Ll =
0.9)
(Ll =
0.91)
0.5
0.91
28
58
4.8
39.6
256
790
0.6
0.96
28
57
4.9
39.8
270
851
0.8
1.18
28
53
5.0
42.7
308
1024
0.5/2.5
1.0
1.37
28
50
5.3
45.4
348
1220
1.5
1.95
28
40
6.2
54.4
435
1740
2.0
2.24
28
36
7.2
65.4
580
2280
2.5
2.50
28
29
7.9
73.6
700
2850
2.0
3.1
110
59
5.04
38.7
262
800
2.5
4.0
110
55
5.13
39.8
280
920
3.0
4.4
110
51
5.37
42.8
312
1008
2/6
3.5
4.8
110
47
5.53
42.8
329
1120
4.0
5.2
110
45
5.72
46.0
360
1216
5.0
5.6
110
41
5.90
50.3
420
1500
6.0
6.0
110
37
6.54
54.9
474
1800
4.0
7.3
230
65
4.92
39.1
268
848
5.0
8.0
230
50
5.20
42.0
305
1020
6.0
8.8
230
47
5.34
44.1
330
1128
4/12
7.0
9.6
230
46
5.35
45.8
364
1260
8.0
10.4
230
43
5.86
49.9
400
1408
10.0
11.2
230
37
6.6
55.5
470
1720
12.0
12.0
230
34
7.00
62.3
528
2064
•
Thermal ca
f
acities for short times other than one second may be calculated on the basis of time being inversely proportional to the
square of t e current.
¢
Degrees current lags voltage at tap value current.
..
Voltages taken with Rectox type voltmeter .
3
www
. ElectricalPartManuals
. com