background image

When  the  main  piston  approaches  the  end  of  its 

stroke,  the  roller  on  the  trip  end  of  the  main  lever 

strikes  the  sloping  face  of  the  latch,  forcing  it  to 

rotate  counter-clockwise  about  its  fulcrum  pin.  As 

the  main  lever  moves  further  down  toward  the 
closed  position,  it  forces  the  pawl  lever  down  thus 

freeing  the  trigger  to  rotate  clockwise  about  its 
fulcrum  pin  so  that  as  the  roller  clears  the  nose  of 

the  latch  and  the  latch  snaps  into  place,  the  trigger 
engages  it  to  prevent  the  release  of  the  roller  and 

opening  of  the  breaker. 

When  the  breaker  is  nearly  closed,  the  "a"  con­

tact  of  the  auxiliary  switch  in  series  with  the 

"Y" 

or  cutoff  contactor  closes.  This  energizes  the 

"Y" 

contactor operating coil, causing it to simultaneously 
open two contacts in  series with the 

"X" 

closing con­

tactor and close a contact which seals in around the 
auxiliary  switch  "a"  contact.  The  opening  of  the 

first  contact  causes  the 

"X" 

coil  to  be  de-energized 

and drop out  its  contacts.  When  the  second  contact 
is  closed,  the 

"Y" 

coil  is  sealed  in  and  is  thus  kept 

energized even in case a fault trips  the breaker  out. 

Since  the  breaker  cannot  close  again  until  the 

"Y" 

contactor  has  been  de-energized  by  opening  the 
control  switch,  pumping  is  prevented. 

A  third  contact  on  the 

"Y" 

contactor  opens  the 

intake  pilot  magnet  circuit  (slightly  ahead  of 

"X" 

contactor  drop-out),  so  that  the  automatic  intake 
valve  piston  returns  immediately  to  the  top  of  its 
cylinder,  thus  allowing  the  intake  valve  itself  to 
close  under  action  of  the  automatic  intake  valve 
spring.  At the same time,  the automatic intake valve 
piston  opens  some  small  ports  in  its  cylinder  wall 

allowing  the  air  in  the  main  cylinder  to  exhaust  to 

atmosphere. 

Simple  Opening. 

Starting with the mechanism 

in  the  closed  position,  when  the  control  switch  on 
the switchboard is turned to  the  "trip" position  (see 
Fig.  3),  the  trip  coil  is  energized  through  the  two 
auxiliary  switch  "a"  contacts.  As  the  trip  plunger 
snaps  upward  to  strike the  trigger,  the  latter  rotates 

counter-clockwise  about  its  fulcrum  pin  to  release 
the  latch,  which  is  forced  back  by  operating  lever 
under  action  of  the  breaker  accelerating  spring. 
As  the  opening  lever  moves  upward,  it  releases  the 
pawl lever spring engaging the trigger, thus keeping 
the  trigger  spring  compressed  and  the  trigger  in 
readiness  for  another  closing  operation. 

Close-Open  Operation- Pneumatic  Trip­

Free  Action. 

If,  at the  time  of closure,  some  con­

dition  exists  which  causes  the  trip  circuit  to  be 
energized,  the  exhaust  pilot  valve  coil  will  also  be 
energized,  simultaneously  opening the exhaust pilot 

VALVE  CLOSED 

VALVE  OPEN 

FIG.  4. 

Operation  of Exhaust  Pilot  Valve 

valve  and permitting  high pressure  air from mecha­
nism  cylinder  to  act  on  the  head  of  the  exhaust 

valve  piston.  The  latter  is  forced  open  as  shown  in 
Fig.  4,  so  that  the  high  pressure  air  in  the  main 
cylinder  is  quickly  exhausted  to  atmosphere.  This 
permits  the  breaker  to  open  quickly  without  dis­
connecting  the  breaker  operating  rods  from  the 
mechanism  piston  and  lever.  See  also  schematic 
diagram  Fig.  5. 

This  differs  from  the  solenoid  mechanism,  with 

which  it  is necessary  (due  to  sluggishness  imparted 
to  the  mechanism  core  by  the  inductive  circuit)  to 
disconnect  the  breaker  pull  rod  from  the  solenoid 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for CAS-8

Page 1: ...C OPERATING MECHANISM Type CAS 8 for Oil Circuit Breakers WESTINGHOUSE ELECTRIC CORPORATION SWITCHGEAR DIVISION EAST PITTSBURGH PLANT EAST PITTSBURGH PA SUPERSEDES 1 8 33 125 1 EFFECTIVE FEBRUARY 1949 Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ... the compressed air closed spring opened type It is pneumatically trip free suitable for ultra high speed reclosing and is appli cable to indoor and outdoor service Application of this mechanism is some times made where high speed reclosing is not required but where it is de sirable to eliminate large batteries required for solenoid mechanisms PNEUMATIC GOVERNOR SWITCH SAFETY VALVE HEATER LATCH TR...

Page 3: ...op dangerously high cylinder pressures The compressor may be dis connected by opening the AB breaker in the motor circuit leaving the heaters energized The closing equipment consists of an air com pressor with a storage tank and automatic control A pneumatic governor is set to maintain the pressure in the storage tank at a certain value the com pressor motor is started when the pressure falls appr...

Page 4: ...ICAL THROTTLE CONTroL EXHAUST PILOT VALVE IN PARALLEL WITH TRIP COIL ADJUST ARMATURE FOR Y32 fREE TRAVEL TOTAL TRAVEL AI R EXHAUST NOTE ADJUST fOR MINIMUM BLEEDER OPENING SO THAT EXHAUST VALVE WILL NOT OPERATE ON NORMAL BREAI ER CLOSING FIG I Cross Sectional View of Type CAS 8 Operating Mechanism tl t i Ul n E l e c t r i c a l P a r t M a n u a l s c ...

Page 5: ...the piston rod which also serves as a guide for the piston see Fig l It should always be removed when the breaker is to be operated by air or tripped from the closed position An external tripping handle is also provided on one side of the housing Auxiliary Switches A 10 pole and a 2 pole type W multi contact rotary auxiliariswitch each in dependently adjusted and mechanically connected to operate ...

Page 6: ...ism has been closed and latched by the hand closing jack and it is desired to open it in the same way hold up on the trip armature while backing off the jack so that the latch will be released otherwise the latch will hold the mechan ism closed Avoid letting the jack part way out be fore releasing the latch as the blow may break the bearing in the jack Always make certain that the jack is removed ...

Page 7: ...ARM VALVE CLOSED 0 FOR L P SPEED X LOW PRESS HEATER _ _Y CUTOUT SW I NOTE HEATERS ARE SHOWN 1 CONNECTED FOR 230 V _j I FOR 115 v SEE DETAIL ___j HI H2 1 1 1 1 1 1 I 17 1 1 OR H R HS NOTES BKR AUX SWS SHOWN FOR OPEN BKR RELAY CONTACTS SHOWN FOR DEENERGIZED RELAY PRESSURE CONTACTS SHOWN FOR OPERATING PRESSURE OPEN CONT OR AUX SW CLOSED CONT OR AUX SW FIG 3 Schematic Wiring Diagram 6cOIL OF DEVICE I ...

Page 8: ...time the automatic intake valve piston opens some small ports in its cylinder wall allowing the air in the main cylinder to exhaust to atmosphere Simple Opening Starting with the mechanism in the closed position when the control switch on the switchboard is turned to the trip position see Fig 3 the trip coil is energized through the two auxiliary switch a contacts As the trip plunger snaps upward ...

Page 9: ... and the full force of the air is available to stop the breaker in its opening stroke and return it to the closed position The speed of breaker reclosing is determined primarily by the point in the opening stroke at which the air is ad mitted This is controlled by the b contact special contact on 2 pole auxiliary switch see diagram Fig 4 which energizes the magnetic pilot valve The sliding station...

Page 10: ...ng an additional washer under each side of the spring mounting block The castle nut on the stud through the springs is for assembly only and should be backed out and locked far enough to allow spring pressure on the latch in either position should be 5 64 6 64 as indicated on Fig 1 and may be adjusted by screwing the trigger stop in or out With the jack just snug and ready to take the load check t...

Page 11: ...ts will require an adjustment on the screw on the top of the slotted link It is best to make these adjustments when the breaker is open in order to make sure that the pin on the main lever is not jammed in the top of the slot Do not change throttle adjustments unless there is some good reason for doing so Opening the throttle wider for faster closing operation will abuse the breaker unnecessarily ...

Page 12: ...t should be investi gated If the mechanism overtravels when the air is applied in this manner it is a reasonably good 12 indication that the leaks are not excessive These leaks are present only when the mechanism oper ates the air is sealed off positively by the intake valve at all other times The throttle piston should be inspected for free operation It is returned to its restricting position by ...

Reviews: