background image

means  of  the  rear  mounting  stud  or  studs  for  projection 
mounting. 

Either  a  mounting  stud  or  the  mounting  screws  may 

be  utilized  for  grounding  the  relay.  The  electrical  connections 
may  be  made  directly  to  the  terminals  by  means  of  screws  for 

steel  panel  mounting  or  the  terminal  studs  furnished  with  the 
relay  for  thick  panel  mounting.  The  terminal  studs  may  be 

easily  removed  or  inserted  by  locking  two  nuts  on  the  stud 

and  then  turning  the  proper  nut  with  a  wrench. 

For  detailed  information,  refer  to  I.L. 

41-076. 

ADJUSTHENT  AND  M.<\INTENANCE 

The  proper  adjustments  to  insure  correct  operation 

cr 

this 

relay  have  been  made  at  the  factory.  Upon  receipt  of  the  relay, 

no  customer  adjustments,  other  than  those  covered  under  "SETTINGS," 
should  be  required. 

_Check 

The  following  check  is  recommended  to  insure  that  the  relay  is 
in  proper  working  order: 

1. 

Contact  Gap  - ThP- contact  gap  should  be  approximately 

. 030". 

2. 

Dropout  Voltage  - The  dropout  voltage  of  the  undervoltage 
relay  can  be  checked  by  applying 

120 

volts  and  then 

decreasing  this  voltage  to  approximately 

100 

volts.  The 

moving  contact  should  make  with  the  right  hand  stationary 

contact  within 

� 

2% 

of  this  value�  Greater  accuracy  can 

be  obtained  by  pre-heating  the  relay  at  normal  line 

voltage  for  approximately  one  hour. 

Close  the  main  relay  contacts  and  pass  sufficient  d-e  current 

through  the  trip  circuit  to  close  the  contacts  of  the 

res. 

This  value  of  current  should  be  between 

and 

1.2 

amperes. 

The  indicator  target  should  drop  freely. 

- 4-

www 

. ElectricalPartManuals 

. com 

Summary of Contents for KV-1

Page 1: ...feed terminal In this case the trip units are supervised by the type KA carrier auxiliary relay to prevent tripping for external faults Hot line reclosing is another application for this relay CONSTRU...

Page 2: ...oving contact arm by a spiral spring The spring adjuster is also held in place by a spring type clamp With the contacts closed the electrical connection is made through the stattionary contact housing...

Page 3: ...or optimum follow and this adjustment should not be disturbed SETTINGS The relay as received has been factory adjusted for 100 volt dropout Any other dropout voltage over the range can be gotten by va...

Page 4: ...adjustments other than those covered under SETTINGS should be required Accept e_ _Check The following check is recommended to insure that the relay is in proper working order 1 Contact Gap ThP contact...

Page 5: ...ure should not be used unless it is apparent that the relay is not in proper working order See Acceptance Check Undervoltage Unit V 1 The upper pin bearing should be screwed down until there is approx...

Page 6: ...til the moving contact just makes with the right hand stationary contact Indicating Contactor Switc ICS Adjust the contact gap for approximately 5 64 1 64 0 Close the main relay contacts and check to...

Page 7: ...EST JACK TERMINAL 185A336 Fig 1 Internal Schematic 0 z 0 ILl _ J I LI 1 50 45 40 35 30 25 20 15 10 5 0 0 J j 1 I v v v v v n l l v 80 V DROPOUT SETTING 100 V DROPOUT SETTING 10 20 30 40 50 60 70 80 90...

Page 8: ...12 MTI ICIEWI 12 y I J PAIIEL COUTOUT I DltU t FOI ISU FWIII Mrl PAIIEI Dill U IK8 011 CUTClll fOit I ROJECTIOII Mh fiOIT YlEW 57 D 7901 Fig 3 Outline and Drilling Type FT 21 Case WESTINGHOUSE ELECTRI...

Page 9: ...ary without having to remove the magnetic core from the frame The electromagnet has two pairs of coils The coils of each pair are mounted diametrically opposite one another In addition there are two l...

Page 10: ...irt moisture excessive vibration and heat Mount the relays vertically by means of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for pro j...

Page 11: ...ionary contact in position With the resistor shorted out pass 15 volts a c through the relay terminals The sensitivity adjustment is made by varying the tension of the spiral spring attached to the mo...

Page 12: ...IC ICS 9 9 9 __Q__ Q___ _____ _ 0 0 0 FRONT VIEW Fig 7 Internal Schematic VARISTOR ltWICATINu COtHACTOR SwiTCti iJOLTA iE UNIT RED HANDLE TEST SWITCt1 TERMI1 AL 184A262 w w w E l e c t r i c a l P a r...

Page 13: ...J a 0 10 5 0 TYPICAL OPERATE TIME CURVES r CONTACT CLOSING L 1 v C NTACT OPENING J 0 2 4 6 8 10 12 14 16 18 20 MULTIPLES OF PICKUP VOLTAGE Fig 2 Typical Operate Time Curves I L 41 933 18 3494A53 5 w w...

Page 14: ...H MTG PANEL CUTOUTS DRILLING PROJEC TION MTG FOR SEMI FLUSH MTG 1 344 SPACERS FOR 34 14 THIN PANELS 5 16 18 SCREW FOR THICK PANELS 594 USE 5 16 18 STUDS J 5 og I DIA 2 HOLES 250 g l6 39 _ 6 35 375 1 0...

Page 15: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 16: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: