4-54
03-19
Relay Output Status Type
Range
【
0
】
:A (Normally open)
【
1
】
:B (Normally closed)
When 03-19=0, and conditions in parameter 03-11, 03-12 are met, relay contact is closed, otherwise relay contact
is open.
When 03-19=1, and conditions in parameter 03-11, 03-12 are met, relay contact is open, otherwise relay contact
is closed.
03-20
Internal / External Multi-Function Input Terminal Selection
Range
【
0~63
】
03-21
Action to Set the Internal Multi-Function Input Terminals
Range
【
0~63
】
Parameter 03-20 allows users to select between external and internal control for multi-function inputs S1-S6.
S
et to 1 for internal control and 0 for external control.
The input selection is based on its decimal value.
DI
S6
S5
S4
S3
S2
S1
Binary
5
2
4
2
3
2
2
2
1
2
0
2
Decimal
32
16
8
4
2
1
The definition of bits in 03-20:
03-20
= 0 0 0 0 0 0
0:
external control (uses parameter 03-00 to 03-05).
S6 S5 S4 S3 S2 S1
1:
internal ON/OFF status control set by parameter 03-21.
The definition of bits in 03-21:
03-21= 0 0 0 0 0 0 0:
I
nternal multi-function input terminal is OFF.
S6 S5 S4 S3 S2 S1 1:
Internal multi-function input terminal is ON.
Example
: Control S2, S4, S6 internally.
1. Set 03-20 = 42 (2+8+32) to set S2, S4 and S6 for internal control, binary representation 101010.
2. Set 03-21 = 10 (2+8), to turn on S2 and S4, binary representation 001010.