4-57
04-External Analog Signal Input / Output Parameters
04-00
Analog Voltage & Current Input Selections AI1/AI2
Range
AI1 AI2
【
0
】
: 0~10V (0~20mA) 0~10V (0~20mA)
【
1
】
: 0~10V (0~20mA) 2~10V (4~20mA)
【
2
】
: 2~10V (4~20mA) 0~10V (0~20mA)
【
3
】
: 2~10V (4~20mA) 2~10V (4~20mA)
Use JP2/JP3 to select analog signal type (voltage or current input).
Parameter 04-00 must be set according to JP2 / JP3 setting.
Analog input scaling:
Current Input Mode
I (mA)
AI (0~20mA)
F Hz
(00 12)
20(mA)
: (
) =
I 4(mA)
AI (4~20mA)
F Hz
(00 12), I
4
20 4(mA)
: (
)=
Voltage Input Mode
V 2(v)
AI(2~10V)
F Hz
(00 12), V
2
10 2(v)
: (
)=
04-01
AI1 Signal Verification Scan Rate
Range
【
1~200
】
2msec
04-02
AI1 Gain
Range
【
0 ~ 1000
】
%
04-03
AI1 Bias
Range
【
0~ 100
】
%
04-04
AI1 Bias Selection
Range
【
0
】
: Positive
【
1
】
: Negative
04-05
AI1 Slope
Range
【
0
】
: Positive
【
1
】
: Negative
04-06
AI2 signal verification Scan Rate
Range
【
1~200
】
2msec
04-07
AI2 Gain
Range
【
0 ~ 1000
】
%
04-08
AI2 Bias
Range
【
0 ~ 100
】
%
04-09
AI2 Bias Selection
Range
【
0
】
: Positive
【
1
】
: Negative
04-10
AI2 Slope
Range
【
0
】
: Positive
【
1
】
: Negative
V(v)
AI (0~10V)
F Hz
(00 12)
10(v)
: (
)=
Downloaded from Dealers Industrial Equipment -- Visit