4-68
Example 1:
Automatic operation mode
– Single cycle
In this example the inverter executes a single cycle and then stops.
Parameter Settings:
06-00 =
1 or 4 (Single cycle operation)
06-32~06-34= 1 (Forward for multi-step speed 0 - 2)
06-35=
2 (Reversal for multi-step speed 3)
06-36~06-47= 0 (Stop for multi-step speed 4 - 15)
05-01=
15 Hz (Multi-step speed 0:15 Hz)
06-01=
30 Hz (Multi-step speed 1:30 Hz)
06-02=
50 Hz (Multi-step speed 2:50 Hz)
06-03=
20 Hz (Multi-step speed 0:20 Hz)
06-16=
20 sec (Multi-step speed 0:20 sec)
06-17=
25 sec (Multi-step speed 1:25 sec)
06-18=
30 sec (Multi-step speed 2:30 sec)
06-19=
40 sec (Multi-step speed 3:40 sec)
05-01
06-01
06-02
06-03
06-16
06-17
06-18
06-19
T
Hz
RUN
command
RUN
ON
S1 to S6 auto
run enable
Figure 4.3.6 Single cycle automatic operation (stop)