4-79
08-10
Output phase lost protection
Range
【
0
】
:Disabled
【
1
】
:Enabled
08-10=0:
Output phase loss detection is disabled.
08-10=1:
Output phase loss detection is enabled. Keypad shows "LF" when an output phase loss is detected and
the inverter output is turned off and the fault contact is activated.
Note:
The output phase loss detection is disabled when the output current is less than 10% of the inverter rated
current.
08-11
Motor type selection:
Range
【
0
】
:Electronic relays protect standard motor
【
1
】
: Electronic relays protect inverter duty motor
08-12
Motor Overload Protection Curve Selection:
Range
【
0
】
:Constant Torque (OL =103 %) (150 % for 1 Minute)
【
1
】
:Variable Torque (OL = 113 %)(123 % for 1 Minute)
When 08-11
=
【
0
】
:
Set 02-06 to the motor nominal frequency.
Motor overload protection levels based on setting of 08-11 and 08-12:
OL1 level
Frequency
(base on rated F)
08-11=0 08-11=0 08-11=1 08-11=1
08-12=0 08-12=1 08-12=0 08-12=1
F<=33.3%
63%
63%
103%
113%
33.3%<F<90%
85%
88%
F>=90%
103%
113%
When 08-12
=
【
0
】
:
Overload protection for motors used in general purpose applications, motor load not to exceed
103% of the motor rated current for the motor to continue to run. If the load is greater than 150% of the motor
rated current, the motor will run for 60 sec before tripping on a motor overload condition. (Curve 1).
When 08-12
=
【
1
】
:
Overload protection for motors used in variable torque applications (HVAC Fan, Pump …),
motor load not to exceed 113% of the motor rated current for the motor to continue to run. If the load is greater
than 123% of the motor rated current, the motor will run for 60 sec before tripping on a motor overload condition.
(Curve 2).
Minute
1.0
150
Current
(1)
(2)
5.0
123
113
103