4-88
10-08
PID Offset
Range
【
0
】
: Positive Direction
【
1
】
: Negative Direction
10-09
PID Offset
Range
【
0
~ 109
】
%
10-08 /10-09: Calculated PID output is offset by 10-09 (the polarity of offset is based on parameter 10-08)
10-10
PID Output Lag Filter Time
Range
【
0.0
~ 2.5
】
Sec
10-10: Low pass filter situated before the PID limit block that can be used to prevent PID output resonance.
Increase the time constant to a value greater than the resonance frequency cycle and reduce time constant to
increase the inverter response.
10-11
Feedback Loss Detection Mode
Range
【
0
】
:Disable
【
1
】
:Enable
– Drive Continues to Operate After Feedback Loss
【
2
】
:Enable
– Drive “STOPS” After Feedback Loss
10-12
Feedback Loss Detection Level
Range
【
0 ~ 100
】
10-13
Feedback Loss Detection Delay Time
Range
【
0.0 ~25.5
】
Sec
PID feedback loss detection
10-11=0:
Disable
10-11=1:
Warning
A feedback loss condition is detected when the PID feedback value falls below the value set in parameter 10-12
(PID feedback loss detection level) for the time set in parameter 10-13 (PID feedback loss detection time). PID
feedback loss warning message "PDER" will be displayed on the keypad and the inverter will continue to operate.
10-11=2:
Fault
A feedback loss condition is detected when the PID feedback value falls below the value set in parameter 10-12
(PID feedback loss detection level) for the time set in parameter 10-13 (PID feedback loss detection time). PID
feedback loss fault message "PDER" will be displayed on the keypad, the inverter stops and the fault contact is
activated.
10-14
Integration Limit Value
Range
【
0 ~ 109
】
%
10-14: PID integral limit:
Used to limit the integral output to prevent motor stall or damage to the system in case
of a rapid change in the feedback signal. Reduce the value of 10-14 to increase the inverter response.