4-93
Notes:
During stall prevention the actual acceleration and deceleration time is based on preset acceleration /
deceleration time + S curve time.
To disabled S curve function set parameter 11-04~11-07 to 0.
Accelerating time = Accelerating time 1 (or 2) + (11-04) + (11-05)
2
Deceleration time = Deceleration time 1 (or 2) + (11-06) + (11-07)
2
11-08
Skip frequency 1
11-09
Skip frequency 2
11-10
Skip frequency 3
Range
【
0.00 ~ 650.00
】
Hz
11-11
Skip frequency range (±frequency band)
Range
【
0.00 ~ 30.00
】
Hz
These parameters allow “skipping over” of certain frequencies that can cause unstable operation due to
resonance within certain applications.
Note:
Prohibit any operation within the skip frequency range. During acceleration and deceleration the frequency
is continuous without skipping the jump frequency.
To enable skip frequency 1
– 3 (11-08 – 11-10) set the frequency to a value greater than 0.0 Hz.
Use the skip frequency range (11-11) to create a skip frequency bandwidth. Refer to figure 4.3.15.
11-11
11-11
11-11
Output
Frequency
Frequency
Reference
11-09
11-08
11-10
Figure 4.3.15 Jump frequency operation