4-96
11-14
Regeneration Prevention Voltage Level
Range
【
230V:300.0~400.0, 460V: 600.0~800.0
】
V
This parameter sets the Regeneration prevention voltage level.
Note:
If this level is set too low over-voltage protection will not work properly and the actual deceleration time will
be extended.
11-15
Regeneration Prevention Frequency Limit
Range
【
0.00~ 15.00Hz
】
Parameter sets the regeneration prevention frequency limit.
11-16
Regeneration Prevention Voltage Gain
Range
【
0~200
】
11-17
Regeneration Prevention Frequency Gain
Range
【
0~200
】
Regeneration prevention response time can be adjusted by increasing 11-16/11-17. This will improve the
response to voltage changes on the DC bus but may cause output frequency instability.
Set 11-16 as low as possible to reduce output frequency instability if this does not correct the instability then
reduce the setting of parameter 11-17.