3-24
General Specifications
Item
E510
Control Mode
V/F Control, Vector Control
Frequency
Output Frequency
0.01~650.00Hz
Starting Torque
150%/1Hz(Vector)
Speed Control Range
1:50
Setting resolution
Digital input: 0.01Hz
Analog input:0.06Hz/60Hz
Setting
Keypad:
Set directly with▲▼ keys or the VR on the
keypad
External Input Terminals:
AI1(0/2~10V), AI2(0/4~20mA)input
Multifunction input up/down function(Group3)
Setting frequency by communication method.
Frequency limit
Lower and upper frequency limits,
3 skip frequency settings.
Run
Operation set
Keypad run, stop button
External terminals:
Multi- operation-mode2 / 3 wire selection
Jog operation
Run signal by communication method.
Main Control
Features
V / F curve setting
18 fixed curves and one customized curve
Carrier frequency
1~16KHz
Acceleration and
deceleration control
2 Acceleration / deceleration time parameters.
4 off S curve parameters.
Multifunction input
29 functions (refer to description on group3)
Multifunction output
21 functions (refer to description on group3)
Multifunction analog
output
5 functions (refer to description on group4)
Main features
Overload Detection,16 preset speeds, Auto-run, Acc/Dec
Switch (2 Stages),Main/Alt run Command select,
Main/Alt Frequency Command selection, PID control,
torque boost, V/F start Frequency, Fault reset, Firemode.
Display
LED
Display: parameter / parameter value / frequency / line
speed / DC voltage / output voltage / output current / PID
feedback / input and output terminal status / Heat sink
temperature / Program Version / Fault Log.
LED Status Indicator
Run / Stop / Forward / Reverse ,and etc.
Protective
Functions
Overload Protection
The relays to protect the motor and the inverter.
(150%/1min)
Over voltage
·220V: >410V ,380V: >820V
Under Voltage
·220V: <190V , 380V: <380V
Momentary Power Loss
Restart
Inverter auto-restart after a momentary power loss.
Stall Prevention
Stall prevention for Acceleration/ Deceleration/
Operation.