4-12
Group 03: External Digital Inputs and Relay Output Functions
No.
Description
Range
Factory
Setting
Unit
Note
( Terminals R1A,R1B, R1C )
03-12
Output Relay RY2.
( Terminals R2A, R2B )
1:Fault
1
2:Setting Frequency Reached
3:Frequency Reached. Set by (3-13±3-14)
4:Output Frequency Detection1(> 3-13)
5:Output Frequency Detection2(< 3-13)
6:Auto Restart
7:Momentary AC Power Loss
8:Rapid Stop
9:Base Block
10:Motor Overload Protection(OL1)
11:Drive Overload Protection(OL2)
12:Over-torque Threshold Level
(OL3)
13:Preset Output Current Reached
(03-15~16)
14:Brake Control (03-17~18)
15:PID Feedback Signal Loss
16:
Single pre-set count (3-22
)
17:
Dual pre-set count (3-22~23)
18:PLC Status Indicator (00-02)
19:PLC control
20:Zero Speed
*6
03-13
Frequency Reached Level
0.00~650.00
0.00
Hz
*1
03-14
Frequency Reached Detection Range
(±)
0.00~30.00
2.00
Hz
*1
03-15
Preset output current reached
0.1~15.0
0.1
A
03-16
Preset output Current detection delay
Time
0.1~10.0
0.1
Sec
03-17
Brake Release
level
0.00~20.00
0.00
Hz
03-18
Brake Engage
Level
0.00~20.00
0.00
Hz
03-19
Relay Output function type
0:A (Normally open)
1:B (Normally close)
0
-
03-20
Internal / external multi-function input
terminal selection
0~63
0
-
03-21
Action to set the internal multi-function
input terminals
0~63
0
-
03-22
Pre-set count 1
0~9999
0
-
03-23
Pre-set count 2
0~9999
0
-
03-24
Output under current detection
0:Disable
0
-
1:Enable
03-25
Output under current detection level
5%~100%
20%
%
03-26
Output under current detection delay
time
0.0~50.0s
20.0
Sec
03-27
Pulse Frequency
0.01~0.20
0.1
kHz
*7
03-28
Pulse Frequency Gain
0.01~9.99
1.00
*6
※
“NO” indicates normally open, “NC” indicates normally closed.