1-1
1. Safety Precautions (English)
1.1 Before supplying Power to the Inverter
Warning
The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for
three phase supply use input terminals (L1(L), L2, L3(N)). Terminals T1, T2, T3 must only be used to
connect the motor. Connecting the input supply to any of the T1, T2 or T3 terminals will cause damage to
the inverter.
Caution
To avoid the front cover from disengaging or other physical damage, do not carry the inverter by
its cover. Support the unit by its heat sink when transporting. Improper handling can damage the
inverter or injure personnel, and should be avoided.
To avoid the risk of fire, do not install the inverter on or near flammable objects. Install on
nonflammable objects such as metal surfaces.
If several inverters are placed inside the same control panel, provide adequate ventilation to
maintain the temperature below 40°C/104°F (50°C/122°F without a dust cover) to avoid
overheating or fire.
When removing or installing the digital operator, turn off the power first, and then follow the
instructions in this manual to avoid operator error or loss of display caused by faulty connections.
Warning
This product is sold subject to IEC 61800-3. In a domestic environment this product may cause radio
interference in which case the user may need to apply corrective measures.