4-31
00-07
Main and Alternative Frequency Command Modes
Range
【
0
】:
Main reference frequency
【
1
】:
Main fre alternative frequency
When set to 0 the reference frequency is set by the main reference frequency selection of parameter 00-05.
When set to 1 the reference frequency is sum of the main reference frequency (00-05) and alternative frequency
(00-06).
Note:
The inverter will display the SE1 error when 00-07 = 1 and parameter 00-05 and 00-06 are set to the same
selection.
When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by parameter 05-01
(Frequency setting of speed-stage 0).
00-08
Communication Frequency Command
– READ ONLY
Range
【
0.00~650.00
】
Hz
Display the frequency reference when 00-05 or 00-06 is set to communication control (3).
00-09
Communication Frequency Command Memory
Range
【
0
】:
Do not store the communication frequency command at power down
【
1
】:
Store communication frequency reference at power down
Note:
This parameter is only effective when frequency reference is set via communication (00-05 / 00-06 = 3).
00-10
Initial Frequency Selection
Range
【
0
】
:By Current Freq Command
【
1
】
:By Zero Freq Command
【
2
】
:By 00-11
00-11
Initial Frequency Setpoint
Range
【
0.00~650.00
】
Hz
Notes:
- This parameter is only effective in keypad mode
- When 00-10=
【
0
】
, the initial frequency will be current frequency.
- When 00-10=
【
1
】
, the initial frequency will be 0.
- When 00-10=
【
2
】
, the initial frequency is set by parameter 00-11.
00-12
Upper Limit Frequency
Range
【
0.01~650.00
】
Hz
Set the maximum frequency reference. Maximum output frequency depends on motor selection.
Motor : Maximum frequency parameter 01-02.
00-13
Lower Limit Frequency
Range
【
0.00~649.99
】
Hz