4-34
01-V/F Control Parameters
01-00
Volts/Hz Patterns (V/F)
Range
【
0~18
】
The V/F curve selection is enabled for V/F mode. Make sure to set the inverter input voltage parameter 01-14.
There are three ways to set V/F curve:
(1) 01-00 = 0 to 17: choose any of the 18 predefined curves (0 to 17).
(2) 01-00 = 18, use 01-02~01-09 and 01-12 ~ 01-13.
The default parameters (01-02 ~ 01-09 and 01-12 ~ 01-13) are the same when 01-00 is set to 18 and 01-00 is set
to 0 (50Hz) or 9 (60Hz) depending on the initialization mode.
Parameters 01-02 ~ 01-13 are automatically set when any of the predefined V/F curves are selected.
This parameter will be affected to reset by the initialization parameter (13-08).
Consider the following items as the conditions for selecting a V/F pattern.
(1) The voltage and frequency characteristic of motor.
(2) The maximum speed of motor.
01-03 (Vmax)
01-05 (Vmid2)
01-07 (Vmid1)
01-09 (Vmin)
01-08
01-06
01-04
01-02
(V)%
Hz
650.00