4-50
03-11
Multifunction Output Relay RY 1 functions. ( Terminals R1C,R1B, R1A )
03-12
Multifunction Output Relay RY 2 functions. ( Terminals R2B, R2A )
Range
【
0
】
:Run
【
1
】
:Fault
【
2
】
:Set Frequency within the preset range. -------------------------------( refer to 03-14)
【
3
】
:Set Frequency reached. As set by (3-13±3-14) -------------- ( refer to 03-13/03-14)
【
4
】
:Output Frequency Detection 1 (> 03-13) ----------( refer to 03-13)
【
5
】
:Output Frequency Detection 2 (< 03-13) ----------( refer to 03-13)
【
6
】
:Auto-restart
【
7
】
:Momentary AC Power Loss
---------------------------------
(
refer to
07-00)
【
8
】
:Rapid Stop ( Decelerate to Stop)
【
9
】
:Base Block Stop Mode
【
10
】
:Motor Overload Protection (OL1)
【
11
】
:Drive Overload Protection (OL2)
【
12
】
:Over Torque Threshold Level (OL3)
【
13
】
:Preset Current level Reached
-------------------------
(
refer to
03-15/03-16)
【
14
】
:Preset Brake Frequency Reached
-----
(
refer to
03-17/03-18)
【
15
】
:PID Feedback Signal Loss
【
16
】
:Single pre-set count (3-22)
【
17
】
:Dual pre-set count (3-22~23)
【
18
】
:PLC status indicator (00-02)
【
19
】
:PLC control
【
20
】
:Zero Speed
03-13
Frequency Reached Level
Range
【
0.00~650.00
】
Hz
03-14
Frequency Reached Detection Range (±)
Range
【
0.00~30.00
】
Hz
Output relay RY function descriptions:
03-11/03-12 =
【
0
】
: Run
Output is active when run command is ON or output frequency is greater than 0
03-11/03-12 =
【
1
】
: Fault
Output is active during fault condition.
03-11/03-12 =
【
2
】
Set Frequency within the preset range
Output is active when the output frequency falls within the frequency reference minus the frequency detection
width (03-14).