41
WHL-015 REV. 5.20.16
SYSTEM CONTROL SETTINGS
MAXIMUM FLAME DETECTING VOLTAGE
2.5V
PRE-PURGE TIME (Tp)
5 seconds
SAFETY TIME (IGNITING TIME) (Ts)
3.5 seconds
IGNITING INTERVAL TIME
10 seconds
POST-PURGE TIME (Tip)
2 minutes (1
st
: 1 minute, 2
nd
: 1 minute)
OVER-HEATING 1,2,3 PROTECTION DETECTION TIME
<3 seconds
PUMP 1 POST CIRCULATING TIME (T1pv)
1 minute
PUMP 2 POST CIRCULATING TIME (T2pv)
1 minute
HIGH AND LOW WATER LEVEL DETECTION TIME
<6 seconds
HIGH AND LOW WATER LEVEL RECOVERY TIME
<6 seconds
Table 20
– System Control Settings