WHL-052 Rev. 4.28.16
12
•
Chlorine concentration less than 100 ppm
•
Using chlorinated fresh water should be acceptable as
levels are typically less than 5 ppm.
•
Do not connect the boiler to directly heat swimming
pool or spa water.
•
Do not fill boiler or operate with water containing
chlorine in excess of 100 ppm.
Figure 4 - Boiler Dimensions - NOTE: All Dimensions Are Approximate
*NOTE:
It is recommended to clean the heat exchanger at
least once a year to prevent lime scale buildup. To clean the
heat exchanger, follow the maintenance procedure in this
manual.
Hardness:
Less than 7 grains
Chloride levels:
Less than 100 ppm
pH levels:
6 - 8
TDS:
Less than 2000 ppm
Sodium:
Less than 20 mGL