WHL-052 Rev. 4.28.16
46
CLOCK HOUR
08/28/2009 Fr 10:01A
Allows the user to adjust the hour
setting.
CLOCK MINUTE
08/28/2009 Fr 10:01A
Adjusts the minute setting.
CLOCK DAY OF WEEK
08/28/2009 Fr 10:01A
Adjusts the day of the week.
CLOCK DATE MODE
08/28/2009 Fr 10:01A
Allows the user to switch to
European date format (2009/08/28)
from US format (08/28/2009).
CLOCK YEAR
08/28/2009 Fr 10:01A
Adjusts the year setting.
CLOCK MONTH
08/28/2009 Fr 10:01A
Adjusts the month setting.
CLOCK DATE
08/28/2009 Fr 10:01A
The clock is set.
Table 17 - Clock Setting Screens
NOTE:
The internal clock does not adjust for daylight savings
time and requires manual adjustment.
E. Programming the System Setting
System Setting Program Access
Note: Programming the boiler control is not possible when
the boiler is firing. Make sure any input which can create a
demand on the boiler, such as the tank thermostat, is turned
off, so the boiler will remain idle to allow programming.
Screen
Description
ENTER MENU CODE
000
To access the boiler setting program,
press and hold
ENTER
for 4 seconds
until the display shows the screen at
left.
ENTER MENU CODE
925
Use the arrow keys to log in the
Boiler Menu Access Code - 925
.
Press
ENTER
to confirm the code
and access the
System Setting
Program
navigation menu.
Table 18 - System Setting Access
F. System Setting Program Navigation
Once the
System Menu Access Code
is confirmed, the user can
begin to set the system setting menu. Use the
< >
keys on the
display to navigate through the System Settings. To change
a setting, press
ENTER
. System settings can be
increased
by
pressing
^
and
decreased
by pressing
v
on the display. When
done, press
ENTER
. The setting will stop blinking and you can
move on to next setting. Press
RESET
to exit programming
and store settings. Listed below are the boiler settings that
can be programmed into the control.
Screen
Description
Function 1
Factory Program Mode
MODE
INDIRECT 1
This indicates that the control is
configured correctly. Do not change
this setting.
Function 3
DHW Tank Max Temp
DHW TANK MAX TEMP
180
o
F 3
This is the maximum temperature
that can be selected in boiler settings
for the DHW tank. Factory Default is
180
o
F. (Range: 95
o
F to 180
o
F)
Screen
Description
Function 6
DHW Post Pump Time
DHW POST PUMP TIME
0 MINUTES 6
The indirect pump has the ability to
post purge energy from the boiler to run
the pump after the set point has been
achieved. Please note that running the
pump for a time greater than 5 minutes
may cause tank energy to be released
back to the heat exchanger. Factory
Default of 0 Minutes. (Range: 0 – 10
minutes)
Function 7
Warm Weather Shutoff
WARM WEATHER OFF
68
o
F 7
When used with an outdoor sensor,
warm weather shut down will disable
the boiler if the programmed outdoor
temperature is exceeded. Default:
68
o
F (Range: 41
o
F to 122
o
F).
Function 8
Min Outdoor Temp
MIN OUTDOOR TEMP
5
o
F 8
Sets the minimum outdoor design
temperature for the system. Default:
5
o
F (Range: -49
o
F to 32
o
F).
Function 9
Max Supply Temp
MAX SUPPLY TEMP
180
o
F 9
Sets the maximum design supply
temperature based on the minimum
outdoor design temperature. Default:
180
o
F (Range: 77
o
F to 190
o
F).
Function 10
Max Outdoor Temp
MAX OUTDOOR TEMP
68
o
F 10
Sets the maximum outdoor design
temperature for the system design.
Default: 68
o
F (Range 32
o
F to 190
o
F).
Function 11
Min Supply Temp
MIN SUPPLY TEMP
95
o
F 11
Sets the design supply water
temperature based on the maximum
outdoor design temperature. Default:
95
o
F (Range: 32
o
F to 190
o
F).
Function 12
Min Boiler Temp
MIN BOILER TEMP
68
o
F 12
Sets the design minimum heat curve
temperature for central heat. Default:
68
o
F (Range: 32
o
F to 190
o
F).
Function 13
CH Post Pump Time
CH POST PUMP TIME
0 MINUTES 13
Allows the user to set the boiler pump
post purge time once the thermostat is
satisfied. Default: 0 minutes (Range: 0
– 10 minutes).
Function 14
DHW Priority
DHW PRIORITY
30 MINUTES 14
Allows the user to set the maximum
run time for the indirect fired water
heater and the minimum run time for
central heating. Default: 30 minutes
(Range: 0 – 60 minutes).
Function 15
Cascade Address
CASCADE ADDRESS
0 15
Bus addressing boilers (maximum
boilers allowed is eight (8) in a cascade
system). Master Boiler address is 0 and
Following Boilers are addressed 1 thru
15. Default: 0 (Range: 0 – 15). NOTE:
ONLY USE ADDRESS 8.
Summary of Contents for WBRE110
Page 13: ...WHL 052 Rev 4 28 16 13 Figure 5 Boiler Dimensions NOTE All Dimensions Are Approximate ...
Page 37: ...WHL 052 Rev 4 28 16 37 Figure 25 Internal Connection Diagram ...
Page 62: ...WHL 052 Rev 4 28 16 62 Figure 30 Combustion System Replacement Parts 80 220kBTU Models ...
Page 63: ...WHL 052 Rev 4 28 16 63 Figure 31 Combustion System Replacement Parts 299 399kBTU Models ...
Page 64: ...WHL 052 Rev 4 28 16 64 Figure 32 Cabinet Replacement Parts All Models ...
Page 65: ...WHL 052 Rev 4 28 16 65 Figure 33 Cabinet Replacement Parts All Models ...