WHL-052 Rev. 4.28.16
56
FLAME LOSS F10
PUMP ON TIME
The flame was lost 3 times while the boiler
was firing during 1 demand call. This is a
serious safety issue as indicated by the
illuminated red light and the word LOCKOUT
flashing on the display. The boiler will not
restart until a technician determines and
repairs the cause of flame loss and pushes
RESET
on the display. During this lockout
fault, the pump will be on.
1. Monitor gas pressure to the unit while in operation.
2. Assure the flame is stable when lit.
3. Check if the display readout changes from “GAS VALVE
ON” to “RUN” within a few seconds of boiler ignition.
4. Check the FLAME signal on the display. It should be
above 2.5uA when the boiler is firing.
5. If the signal reads less than 2.5uA, clean the spark
probe.
6. If the problem persists and the ‘FLAME” signal is still
less than 2.5uA, replace the spark igniter probe.
7. The flame signal should be steady after the boiler has
been firing for 1 minute and is normally at 5.0 to 9.0. If the
flame signal is not steady, disassemble the burner door
and check the burner and its sealing gaskets.
FALSE FLAME SIG F11
PUMP ON TIME
There is flame when the control is not telling
the boiler to run. This is a serious safety issue
as indicated by the illuminated red light and
the word LOCKOUT flashing on the display.
The boiler will not restart until a technician
determines and repairs the cause and pushes
RESET
on the display. During this lockout
fault, the pump will be on.
1. Look into window. If there is flame, turn the gas off to
the unit at the service valve and replace the gas valve.
2. If the flame signal on the status menu is greater than
2.5uA when the burner is not lit, replace the spark ignitor.
3. If the flame signal is not present after turning off the gas
supply, check the gas valve electrical connection.
4. Check for condensate backup. Repair condensate
system as necessary. If condensate has partially filled
the combustion chamber, the refractory wall may be
damaged and should be replaced.
5. Turn the gas on at the service valve after corrective
action is taken.
6. If the refractory wall falls against the spark ignitor, it
may conduct the signal to ground, giving a false reading.
FAN SPEED ERROR F13
PUMP ON TIME
The fan is not running at the speed
determined by the control. Fan speed has
been more than 30% faster or slower than
the commanded speed for more than 10
seconds. This is a serious safety issue as
indicated by the illuminated red light and
the word LOCKOUT flashing on the display.
This boiler will not restart until a technician
determines and repairs the cause and pushes
RESET
on the display. During this lockout
fault, the pump will be on.
1. Check the combustion fan wiring.
2. Measure DC voltage from the red fan wire to ground
while it is connected to the fan. It should be between 24
and 40 volts. If it is lower than 24 volts, check for excessive
external loads connected to the boiler sensor terminals
3. Disconnect the 5 pin plug from the fan and check the
voltage on the red wire again. If it is now between 24-40
volts, replace the fan. If it is still below 24 volts replace the
boiler control board.
FLUE LIMIT F17
PUMP ON TIME
F17 indicates the boiler flue temperature is
excessive. When accompanied by the red
FAULT light and LOCKOUT flashing on the
display, this code indicates the flue sensor
temperature has exceeded 210
o
F and a
serious safety issue exists. The boiler will
not restart until a technician determines and
repairs the cause of excessive temperature
and pushes
RESET
on the display.
1. Check the flue for obstructions and any sign of damage,
especially signs of excessive heat. Repair as necessary.
2. Run the boiler and check the flue temperature with
an external thermometer. If the flue temperature on the
thermometer does not agree with the flue temperature
displayed in the status menu, inspect the wiring to the flue
temperature sensor in the boiler and repair as necessary.
If the wiring is intact replace the flue sensor.
3. If the flue temperature is excessive on the status menu
and the test thermometer reads the same, check and
adjust combustion controls on the boiler.
CONDENSATE FULL F20
PUMP OFF TIME
The condensate trap is full. This is a serious
safety issue as indicated by the illuminated
red light and the word LOCKOUT flashing on
the display. The boiler will not restart until a
technician determines and repairs the cause
and pushes
RESET
on the display. During this
lockout fault, the pump will be off.
1. Check condensate lines for obstructions.
2. Check float switch in condensate reservoir.
3. Check wiring from condensate reservoir to 928 control
and repair as necessary.
Summary of Contents for WBRE110
Page 13: ...WHL 052 Rev 4 28 16 13 Figure 5 Boiler Dimensions NOTE All Dimensions Are Approximate ...
Page 37: ...WHL 052 Rev 4 28 16 37 Figure 25 Internal Connection Diagram ...
Page 62: ...WHL 052 Rev 4 28 16 62 Figure 30 Combustion System Replacement Parts 80 220kBTU Models ...
Page 63: ...WHL 052 Rev 4 28 16 63 Figure 31 Combustion System Replacement Parts 299 399kBTU Models ...
Page 64: ...WHL 052 Rev 4 28 16 64 Figure 32 Cabinet Replacement Parts All Models ...
Page 65: ...WHL 052 Rev 4 28 16 65 Figure 33 Cabinet Replacement Parts All Models ...