3.
Carefully remove the carbon deposits from the spark
arrestor screen with a wire brush. The spark arrestor
must be free of breaks and tears. Replace the spark
arrestor if damaged.
4.
Reinstall the spark arrestor and muffler cover.
FUEL VALVE MAINTENANCE
The fuel valve is equipped with an inline fuel filter. The
fuel valve filter does not require servicing if the unit
is properly maintained with fresh, clean fuel. If fuel-
related troubleshooting is required, perform fuel valve
maintenance.
1.
Allow the generator to cool completely.
2.
Place an appropriate gasoline container under the
carburetor drain bolt to catch the drained fuel.
3.
Remove the drain bolt on the bottom of the carburetor
and allow the fuel tank to drain completely. Install and
tighten the drain bolt securely.
4.
Remove the fuel line from the fuel valve. Be prepared to
capture the remaining fuel from the fuel line.
5.
Loosen the retaining bolt. Unscrew and remove the fuel
valve from the fuel tank. Be prepared to capture any
remaining fuel from the fuel tank.
6.
Open the fuel valve. Use compressed air to clean the
fuel filter and the fuel passage from the fuel line side of
the passage.
7.
Install and tighten the fuel valve until it has a few threads
remaining and is facing outward.
8.
Hold it in place and tighten the retaining bolt.
DO NOT
overtighten.
9.
Replace the fuel line and secure with the clamp.
STORAGE
Proper storage preparation is required for trouble-free
operation and generator longevity.
NOTICE
Gasoline stored for as little as 30 days can deteriorate,
causing gum, varnish, and corrosive buildup in fuel lines,
fuel passages, and the engine. This corrosive buildup
restricts the flow of fuel, which can prevent the engine
from starting after a prolonged storage period. The use
of fuel stabilizer significantly increases the storage life of
gasoline. Full-time use of fuel stabilizer is recommended.
Follow the manufacturer’s instructions for use.
STORAGE TIME
RECOMMENDED PROCEDURE
Less than 1 month
No service required.
2 to 6 months
Fill with fresh gasoline and add
gasoline stabilizer. Drain the
carburetor float bowl.
6 months or longer
Drain the fuel tank and carburetor
float bowl.
SHORT TERM STORAGE
• Allow the generator to cool a minimum of 30 minutes
before storage.
• If operating on propane, turn the propane tank valve
to the fully closed position and disconnect the LPG/
propane hose from the generator and propane tank.
• Replace all protective covers on the generator control
panel.
• Wipe the generator with a moist cloth. Clean any debris
from the muffler cooling vents.
• Store the generator in a well-ventilated, dry location
away from sparks, open flames, pilot lights, heat, and
other sources of ignition such as areas with a spark-
producing electric motor or where power tools are
operated.
•
DO NOT
store the generator, gasoline, or propane tanks
near furnaces, water heaters, or any other appliances
that produce heat or have automatic ignitions.
• With the engine and exhaust system cool and all
surfaces dry, cover the generator to keep out dust.
DO
NOT
use a plastic sheet as a dust cover. Non-porous
materials trap moisture and promote rust and corrosion.