Westinghouse Portable Power | 29
WARNING
Before attempting to service or troubleshoot the generator, the owner or service technician must first read the owner’s
manual and understand and follow all safety instructions. Failure to follow all instructions may result in conditions that
can lead to voiding of the EPA certification or product warranty, serious personal injury, property damage or even death.
TROUBLESHOOTING
PROBLEM
POTENTIAL CAUSE
SOLUTION
Engine is running, but no
electrical output
1. Circuit breakers are tripped.
1. Reset the circuit breakers and check
for overload condition.
2. The power cord’s plug connector is not
fully engaged in the generator’s outlet.
2. Verify plug connector is firmly engaged
in the generator’s outlet. If using the
240V outlet, make sure plug connector
is rotated 1/4 turn in the clockwise
direction.
3. Faulty or defective power cord
3. Replace power cord.
4. Faulty or defective electrical appliance
4. Try connecting a known good
appliance to verify the generator is
producing electrical power.
5. GFCI outlet is tripped
5. Press the reset button on the GFCI
outlet.
6. If trying 1-5 above does not solve
the problem, the cause might be the
generator has a fault.
6. Take the generator to your nearest
authorized service dealer.
Engine will not start or
remain running while
trying to start.
1. Fuel shutoff valve is in the OFF
position.
1. Move the fuel shut off valve to the ON
position.
2. Generator is out of gasoline.
2. Add gasoline to the generator.
3. Fuel flow is obstructed.
3. Inspect and clean fuel delivery
passages.
4. Starting battery may have insufficient
charge
4. On electric start models only. Check
battery output and charge battery as
necessary.
5. Dirty air filter
5. Check and clean the air filter.
6. Low oil level shut down switch is
preventing the unit from starting.
6. Check oil level and add oil if
necessary.
7. Spark plug boot is not fully engaged
with the spark plug tip.
7. Firmly push down on the spark plug
boot to ensure the boot is fully engaged
8. Spark plug is faulty.
8. Remove and check the spark plug.
Replace if faulty.
9. Dirty/plugged spark arrestor
9. Check and clean the spark arrestor.
10. Stale fuel
10. Drain fuel and replace with fresh fuel.
11. If trying 1-11 above does not solve
the problem, the cause might be the
generator has a fault.
11. Take the generator to your nearest
authorized service dealer.
Summary of Contents for WGen7500
Page 1: ...USER MANUAL WGen7500 Portable Generator 7500 Running Watts 9500 Peak Watts REMOTE START...
Page 8: ...8 Westinghouse Portable Power SAFETY SAFETY LABELS AND DECALS 8 9 7 10 8 9 6 6 7 5 10...
Page 31: ...Westinghouse Portable Power 31 WGen7500 SCHEMATIC...
Page 32: ...32 Westinghouse Portable Power WGen7500 EXPLODED VIEW...
Page 37: ...Westinghouse Portable Power 37 Version 07 31 18KD...