Westinghouse Outdoor Power Equipment, LLC | 17

BREAK-IN PERIOD

For proper break-in, 

DO NOT

  exceed  50%  of  the  rated 

running  watts  (3750  watts)  during  the  first  five  hours  of 

operation.
Vary the load occasionally to allow stator windings to heat 

and cool and help seat the piston rings. 

BEFORE STARTING THE GENERATOR

Verify that:

•  The generator is placed in an safe, appropriate location. 
• 

The generator is on a dry, flat, and level surface.

• 

The engine is filled with oil.

•  All loads are disconnected.

DANGER

Fire and explosion hazard. 

DO NOT

 move or tip the 

generator during operation.

STARTING THE ENGINE 

1. 

Verify that gasoline is in the fuel tank. 

2. 

Turn the fuel tank valve to the ON position. 

3. 

Push the battery switch to the ON position. 

4. 

Choose the starting method:

a. Remote Start:

 Push and hold the START button on 

the remote start key fob for one second. 

Note: 

Remote start-equipped generators must be restarted 

with the START/STOP switch on the control panel 

after an automatic shut-down occurs.

b. Push-Button Start: 

Push and hold the engine 

START/STOP button for two seconds. 

c. Recoil Start:

 Manually close the choke if the engine 

is cold. Firmly grasp and pull the recoil handle slowly 

until you feel increased resistance, then pull rapidly. 

Note: 

During Push-Button or Remote Start the engine 

will automatically set the choke and begin the start 

sequence. If the engine fails to start, the generator 

will attempt to start the engine two more times.

STOPPING THE ENGINE

1. 

Turn off and unplug all connected electrical loads. 

IMPORTANT: NEVER

 start or stop the generator with 

electrical devices connected. 

2. 

Let the generator run with no load for several minutes to 

stabilize internal temperatures of the engine. 

3. 

Push and hold the START/STOP button for one second 

or push STOP on the remote start key fob for one 

second.  

Note: 

Alternately, if the generator is used infrequently, turn 

the fuel tank valve to the OFF position to limit the 

residual fuel remaining in the carburetor float bowl. 

The engine will stop when fuel in the carburetor and 

fuel line is exhausted. 

4. 

Push the battery switch to the OFF position.

5. 

If operating on LPG, turn the propane tank valve to the 

fully closed position. 

FREQUENCY OF USE

If the generator will be used on an infrequent or intermittent 

basis (more than one month before next use), refer to 

the Battery Maintenance and Storage sections of this 

manual for information regarding battery charging and fuel 

deterioration. 

AC CIRCUIT BREAKERS

The circuit breakers will automatically switch OFF if there 

is a short circuit or a significant overload of the generator 

at each receptacle.  
If an AC circuit breaker switches OFF automatically, 

check that the appliance is working correctly and it does 

not exceed the rated load capacity of the circuit before 

resetting the AC circuit breaker ON. 

OPERATION

Summary of Contents for WGen7500c

Page 1: ...SER MANUAL DO NOT RETURN THIS PRODUCT TO THE STORE If you have questions or need assistance please call customer service at 855 944 3571 WGen7500c Portable Generator 7500 Running Watts 9500 Peak Watts...

Page 2: ...anual can result in serious injury or death SAVE THESE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION DISCLAIMERS 2 ALL RIGHTS RESERVED 2 SPECIFICATIONS 3 SAFETY SAFETY DEFINITIONS 4 SAFETY SYMBOLS 4 SAF...

Page 3: ...s up to 104 F 40 C If needed this product can be operated at temperatures ranging from 5 F 15 C 122 F 50 C for short periods If the product is exposed to temperatures outside of this range during stor...

Page 4: ...voided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Indicates a situation which can cause damage...

Page 5: ...ly installed and the electrical output has been verified by a qualified electrician The connection must isolate the generator power from utility power and must comply with all applicable laws and elec...

Page 6: ...allow the generator s gas tank to overflow when filling Shut down the engine and allow it to cool for two minutes before adding gasoline or oil to the generator NEVER remove the fuel cap when the gene...

Page 7: ...ttery powered carbon monoxide alarm s in your home WARNING Automatic shutoff accompanied with a flashing RED light in the CO Sensor portion of the control panel is an indication that the generator was...

Page 8: ...the TEST C button located on the front of the receptacle to trip the device This should immediately stop the flow of electricity and shut off the lamp If the electricity is not stopped DO NOT use this...

Page 9: ...Westinghouse Outdoor Power Equipment LLC 9 SAFETY LABELS AND DECALS SAFETY...

Page 10: ...s Receptacles can supply a maximum of 20 Amps 6 120 Volt AC 20 Amp Duplex GFCI NEMA 5 20R Receptacles Receptacles can supply a maximum of 20 Amps 7 20 Amp AC Circuit Breakers Circuit breakers limits t...

Page 11: ...Westinghouse Outdoor Power Equipment LLC 11 COMPONENTS GENERATOR COMPONENTS...

Page 12: ...Assembly wrench Wheel and mounting foot components Item Quantity Mounting foot 2 Flange bolt M8 4 Wheel 2 Axle pin 2 Washer 2 Cotter pin 2 If any parts are missing contact our service team at service...

Page 13: ...fuel item that is broken cut torn or damaged DANGER Fire and explosion hazard DO NOT overfill fuel tank Fill only to the red fill ring located in the in tank fuel screen filter Overfilling may cause f...

Page 14: ...e red maximum fill ring on the fuel screen filter visible in the filler neck 5 Install the fuel cap NOTICE Fuel can damage paint and plastic Use caution when filling the fuel tank Damage caused by spi...

Page 15: ...tairs next to walls or buildings or in any other location that will not allow for adequate cooling of the generator and or the muffler DO NOT contain generators during operation DANGER Asphyxiation ha...

Page 16: ...anel If your unit was shipped without a key fob contact Westinghouse customer service The generator can be started remotely from up to 99 feet 30 meter using the remote start key fob Note As the batte...

Page 17: ...he choke and begin the start sequence If the engine fails to start the generator will attempt to start the engine two more times STOPPING THE ENGINE 1 Turn off and unplug all connected electrical load...

Page 18: ...Conditioner 11 000 BTU 1010 1600 TV Tube Type 300 0 RV Refrigerator 180 600 Radio 200 0 Light 75 Watts 300 0 Coffee Maker 600 0 2590 Total Running Watts 1600 Highest Starting Watts Total Running Watts...

Page 19: ...resulting in death or serious injury Before connecting an AC appliance or power cord to the generator Use grounded 3 prong extension cords tools and appliances or double insulated tools and appliance...

Page 20: ...unit level during transport to minimize the possibility of fuel leakage or if possible drain the fuel or run the engine until the fuel tank is empty before transport The generator wheels are only int...

Page 21: ...ime Hours The maintenance codes will be displayed until the unit is turned off Refer to the Maintenance section for specific procedures Maintenance Code Required Maintenance P25 Change engine oil P50...

Page 22: ...eather change the oil more frequently Ambient air temperature will affect engine oil performance Change the type of engine oil used based on weather conditions Check the engine oil level before each u...

Page 23: ...the spark boot directly away from the engine 3 Clean the area around the spark plug 4 Remove the spark plug with the included spark plug socket wrench NOTICE NEVER apply any side load or move the spa...

Page 24: ...nnect the quick connect plug NOTICE Dispose of the used battery properly according to the guidelines established by your local or state government STORAGE Proper storage preparation is required for tr...

Page 25: ...Start the generator and allow it to run until the generator engine stops 5 Push the battery switch to the OFF position 6 Disconnect the battery quick connect plugs 7 Remove the spark plug 8 Put a teas...

Page 26: ...rocker arms should be loose at TDC on the compression stroke If they are not rotate the engine 360 5 Insert a feeler gauge between the rocker arm and the valve stem to measure valve clearance Intake...

Page 27: ...service toll free at 1 855 944 3571 Engine starts then shuts down Out of fuel Refuel Incorrect engine oil level Check engine oil level Dirty air filter Clean the air filter Contaminated fuel Drain th...

Page 28: ...28 Westinghouse Outdoor Power Equipment LLC EXPLODED VIEWS AND PARTS LISTS EXPLODED VIEW A EXPLODED VIEWS...

Page 29: ...MBLY 9 1 271005 CYLINDER HEAD 9 2 271702 INTAKE VALVE 9 3 275902 EXHAUST VALVE NO PART DESCRIPTION 9 4 261807 INTAKE VALVE SPRING LOWER SEAT 9 5 93513 VALVE SEAL 9 6 266002 VALVE SPRING 9 7 260802 VAL...

Page 30: ...WHEEL NUT 15 RECOIL STARTER ASSEMBLY 15 1 91325 BOLT M6X12 15 2 264738 221B STARTER ASSEMBLY 15 2 1 5910 221 RECOIL STARTER 15 2 2 5943 HANDLE 16 STARTER MOTOR ASSEMBLY 16 1 97415 STARTING MOTOR 16 2...

Page 31: ...Westinghouse Outdoor Power Equipment LLC 31 EXPLODED VIEW B EXPLODED VIEWS...

Page 32: ...120030 ENGINE ASSEMBLY 4 3 549603 DUST BOARD 4 4 91322 BOLT M5X12 4 5 90016 NUT M6 4 6 539602 CRANKCASE COVER 5 CARBON CANNISTER ASSEMBLY NO PART DESCRIPTION 5 1 95123 CARBON CANISTER AND FUEL TANK C...

Page 33: ...23 BOLT M5X16 10 14 544610 SHORT WIRE 11 BATTERY BRACKET ASSEMBLY 11 1 91327 BOLT M6X12 11 2 542614 116 BATTERY PRESSURE PLATE 11 3 512058 BATTERY WIRING ASSEMBLY 11 4 91325 BOLT M6X12 12 CO MODULE AS...

Page 34: ...34 Westinghouse Outdoor Power Equipment LLC SCHEMATICS SCHEMATICS SCHEMATICS...

Reviews: