MAINTENANCE
rCD saFEtY sWitCH tEsting
(iF EquiPPED)
1. Start the generator as described in Starting the
Generator on page 21, but do not connect any
electrical cords or devices into the 240-Volt AC
and/or 12-Volt DC outlets.
2. Turn the locking screw on the RCD safety switch
cover anti-clockwise by hand (see Figure 50) until
the cover is released.
Figure 50 – Opening the RCD Safety Switch Cover
3. Pull forward on the bottom of the RCD safety
switch cover and pivot it upwards to open.
4. Check the RCD safety switch circuit breaker is in
the upwards ON position (see Figure 51).
Figure 51 – RCD Safety Switch Controls
5. Push the yellow TEST button momentarily. The
RCD safety switch circuit breaker should instantly
flick downwards to the OFF position; this indicates
that the RCD safety switch is functioning correctly.
!
WARNING
If the RCD safety switch fails the TEST
function, either by the circuit breaker
not moving to the OFF position at all
or by doing so in a slow or delayed
manner, the generator should not be
used. Stop the generator as described
in Stopping the Generator on page 24
and take it to your nearest authorized
Westinghouse service dealer.
6. If the RCD safety switch passes the TEST
function, push the circuit breaker switch back
upwards to the ON position. Close the cover and
secure it in place by turning the locking screw
clockwise by hand. The generator is now ready for
use.