background image

CONNECTION

4

 

Figure S7 – Pre-assembling the Cable, Gland,

Gland Plate and Mounting Gasket

8.  Connect the generator’s active, neutral and earth 

wires to the corresponding cable conductors 

using your preferred method, e.g. crimp fittings, 

screw connectors, soldering, etc. 

See Figure S8

.

Figure S8 – Connecting the Cable

9.  Adjust the position of the cable within the gland 

so that only a minimum length of cable will 

protrude into the control panel and then tighten 

the gland by hand or with a tool as appropriate. 

Apply a small continuous bead of silicone sealant 

around the circumference of the gland plate on 

the face that will abut the control panel. Align 

the gland plate’s mounting holes with the socket 

mounting holes in the control panel and then affix 

the plate using the screws and washers supplied 

in the cable gland plate kit 

(see Figure S9)

. Wipe 

off any excess sealant from around the gland 

plate.

Figure S9 – Affixing the Gland Plate

to the Control Panel

10.  The other end of the cable MUST be safely 

terminated BEFORE the generator can be 

returned to operation as described below in                  

Step 11. According to the application, for 

example, the other end of the cable may be 

terminated in a 32 A socket, changeover / 

isolating switch, circuit breaker or switchboard.  

11.  Reconnect the generator’s battery cables to the 

battery starting with the positive (+) cable first.  

Re-attach the spark plug boot to the spark plug. 

Plug in any electrical cord or appliance to the 

left-hand-side 240-Volt AC socket and also to the   

12-Volt DC socket, as required 

(see Figure S10)

Figure S10 – 240 Volt AC Detachable Plug & Socket

Connection (Left) and Direct Connection (Right)

The generator is now ready for operation as described 

in the main Instruction Manual. 

Reviews: