5/12/2017
TECH-538/D.W.O. 23160
Page 33 of 189
Figure 4-3 – Electrical Connections ICoT 6400
Figure 4-4 – Example of ICoT 5400 Foundation Fieldbus network topology
Any FM
Approved
Associated
Apparatus
suitable for
FISCO Concept
ICOT 5400
(AVID-SMARTCAl FF)
UI (Vmax) = 17.5V
Ii (Imax) = 380mA
PI (Pmax) = 5.32W
Ci ≤ 5nF
Li = 10uH
Temperature
Classification
T4
ICOT 5400
(AVID-SMARTCAl FF)
UI (Vmax) = 17.5V
Ii (Imax) = 380mA
PI (Pmax) = 5.32W
Ci ≤ 5nF
Li = 10uH
Temperature
Classification
T4
Class I, Zone 0, Ex Ia IIC T4
Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1
HAZARDOUS (CLASSIFIED) LOCATION NONHAZARDOUS LOCATION
Any FM
Approved
Intrinsically
Safe Apparatus
suitable for
FISCO Concept
FF Terminator